GE Multilin
C60 Breaker Protection System
5-197
5 SETTINGS
5.8 INPUTS/OUTPUTS
5
Example 1: Extending input/output capabilities of a C60 relay
Consider an application that requires additional quantities of digital inputs or output contacts or lines of programmable logic
that exceed the capabilities of a single UR-series chassis. The problem is solved by adding an extra UR-series IED, such
as the C30, to satisfy the additional inputs/outputs and programmable logic requirements. The two IEDs are connected via
single-channel digital communication cards as shown below.
Figure 5–94: INPUT AND OUTPUT EXTENSION VIA DIRECT INPUTS AND OUTPUTS
Assume contact input 1 from UR IED 2 is to be used by UR IED 1. The following settings should be applied (Direct Input 5
and bit number 12 are used, as an example):
The
Cont Ip 1 On
operand of UR IED 2 is now available in UR IED 1 as
DIRECT INPUT 5 ON
.
Example 2: Interlocking busbar protection
A simple interlocking busbar protection scheme can be accomplished by sending a blocking signal from downstream
devices, say 2, 3 and 4, to the upstream device that monitors a single incomer of the busbar, as shown in the figure below.
Figure 5–95: SAMPLE INTERLOCKING BUSBAR PROTECTION SCHEME
Assume that Phase Instantaneous Overcurrent 1 is used by Devices 2, 3, and 4 to block Device 1. If not blocked, Device 1
would trip the bus upon detecting a fault and applying a short coordination time delay.
The following settings should be applied (assume Bit 3 is used by all 3 devices to sent the blocking signal and Direct Inputs
7, 8, and 9 are used by the receiving device to monitor the three blocking signals):
UR IED 2:
DIRECT OUT 3 OPERAND
: "
PHASE IOC1 OP
"
UR IED 3:
DIRECT OUT 3 OPERAND
: "
PHASE IOC1 OP
"
UR IED 4:
DIRECT OUT 3 OPERAND
: "
PHASE IOC1 OP
"
UR IED 1:
DIRECT INPUT 7 DEVICE ID
: "2"
DIRECT INPUT 7 BIT NUMBER
: "3"
DIRECT INPUT 7 DEFAULT STATE
: select "On" for security, select "Off" for dependability
DIRECT INPUT 8 DEVICE ID
: "3"
DIRECT INPUT 8 BIT NUMBER
: "3"
DIRECT INPUT 8 DEFAULT STATE
: select "On" for security, select "Off" for dependability
UR IED 1:
DIRECT INPUT 5 DEVICE ID
= “2”
DIRECT INPUT 5 BIT NUMBER
= “12”
UR IED 2:
DIRECT OUT 12 OPERAND
= “Cont Ip 1 On”
UR IED 1
T
X
1
R
X
1
UR IED 2
T
X
1
R
X
1
842712A1.CDR
UR IED 1
UR IED 2
UR IED 4
UR IED 3
BLOCK
Summary of Contents for C60 UR series
Page 2: ......
Page 4: ......
Page 11: ...GE Multilin C60 Breaker Protection System xi TABLE OF CONTENTS INDEX...
Page 12: ...xii C60 Breaker Protection System GE Multilin TABLE OF CONTENTS...
Page 32: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Page 50: ...2 18 C60 Breaker Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Page 128: ...4 30 C60 Breaker Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4...
Page 394: ...9 4 C60 Breaker Protection System GE Multilin 9 1 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Page 516: ...D 10 C60 Breaker Protection System GE Multilin D 1 OVERVIEW APPENDIXD D...
Page 528: ...E 12 C60 Breaker Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E...