2–10
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 2: INTRODUCTION
Timing accuracy: ...........................................+50 ms
Elements:............................................................Trip
REDUCED VOLTAGE START
Transition level: ..............................................25 to 300% FLA in steps of 1
Transition time: ...............................................1 to 600 s in steps of 1
Transition control: .........................................Current, Timer, Current and Timer
RESTART BLOCK
Time delay:........................................................1 to 50000 s in steps of 1
Timing accuracy: ...........................................±0.5 s or ±0.5% of total time
Elements:............................................................Block
RTD
Pickup: .................................................................1 to 250°C in steps of 1
Pickup hysteresis: ..........................................2°C
Time delay:........................................................3 s
Elements:............................................................Trip and Alarm
UNDERCURRENT
Pickup level:.......................................................0.10 to 0.95
×
CT primary in steps of 0.01 of any one
phase
Time delay:........................................................1 to 60 s in steps of 1
Block from start: ............................................0 to 15000 s in steps of 1
Pickup accuracy: ...........................................as per phase current inputs
Timing accuracy: ...........................................±0.5 s or ±0.5% of total time
Elements:............................................................Trip and Alarm
UNDERVOLTAGE
Pickup Level:
Motor starting: .............................................0.60 to 0.99
×
Rated in steps of 0.01
Motor running: .............................................0.60 to 0.99
×
Rated in steps of 0.01 of any one phase
Time delay:........................................................0.1 to 60.0 s in steps of 0.1
Pickup accuracy: ...........................................as per voltage inputs
Timing accuracy: ...........................................<100 ms or ±0.5% of total time
Elements:............................................................Trip and Alarm
VOLTAGE PHASE REVERSAL
Configuration: .................................................ABC or ACB phase rotation
Timing Accuracy: ...........................................500 to 700 ms
Elements:............................................................Trip
2.2.4
Digital Inputs
DIGITAL COUNTER
Configuration: .................................................assign to digital inputs 1 to 4
Frequency:
.............................................≤
50 times a second
Range:..................................................................0 to 1 000 000 000
Elements:............................................................Alarm
GENERAL PURPOSE SWITCH
Configuration: .................................................assign to digital inputs 1 to 4
Time delay:........................................................0.1 to 5000.0 s in steps of 0.1
Block from start: ............................................0 to 5000 s in steps of 1
Timing accuracy: ...........................................±250 ms or ±0.5% of total time
Summary of Contents for 469
Page 62: ...2 16 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 2 INTRODUCTION ...
Page 90: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Page 292: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Page 313: ...A APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A 7 HGF5C 808841A1 HGF8 808842A1 ...
Page 315: ...A APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A 9 808712A1 CDR ...
Page 320: ...A 14 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A APPENDIX ...