6–16
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 6: ACTUAL VALUES
The values for analog inputs are shown here. The name of the input and the units will
reflect those programmed for each input. If no analog inputs are programmed in
S12
ANALOG I/O
Z
ANALOG INPUT 1(4)
, the
THIS FEATURE NOT PROGRAMMED
flash
message will appear when an attempt is made to enter this group of messages.
6.3.8
Phasors
PATH: ACTUAL VALUES
ZV
A2 METERING DATA
ZV
PHASORS
The 469 Motor Management Relay was designed to display lagging angles. Therefore, if a
system condition would cause the current to lead the voltage by 45°, the 469 relay will
display such angle as 315° Lag instead of 45° Lead.
Note
When the currents and voltages measured by the relay are zero, the angles displayed
by the relay and those shown by the EnerVista 469 Setup software are not fixed values.
The EnerVista 469 Setup software is a useful tool to view the vectors seen by the relay in
graphical format. The same information described above is displayed by the EnerVista 469
Setup software as follows:
MESSAGE
ANALOG 3-4
0 Percent
Range: –5100 to 4900%. Seen only if
Analog In Diff 3-4 set to %Diff
MESSAGE
ANALOG 3-4
0 Units
Range: –100000 to 100000. Seen only
if Analog In Diff 3-4 is Abs Diff
PHASORS
[
Z
]
Va PHASOR
0.0% AT 0°Lag
MESSAGE
Vb PHASOR
0.0% AT 0°Lag
MESSAGE
Vc PHASOR
0.0% AT 0°Lag
MESSAGE
Ia PHASOR
0.0% AT 0°Lag
MESSAGE
Ib PHASOR
0.0% AT 0°Lag
MESSAGE
Ic PHASOR
0.0% AT 0°Lag
Summary of Contents for 469
Page 62: ...2 16 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 2 INTRODUCTION ...
Page 90: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Page 292: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Page 313: ...A APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A 7 HGF5C 808841A1 HGF8 808842A1 ...
Page 315: ...A APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A 9 808712A1 CDR ...
Page 320: ...A 14 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A APPENDIX ...