5-57
5 SETTINGS
5.2 PRODUCT SETUP
5
o) IEC 60870-5-104 PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 60870-5-104 PROTOCOL
The F60 supports the IEC 60870-5-104 protocol. This protocol is enabled when the
SETTINGS
PRODUCT SETUP
COM-
MUNICATIONS
PROTOCOL
setting is set to IEC 60870-5-104. The F60 can be used as an IEC 60870-5-104 slave device
connected to a maximum of two masters (usually either an RTU or a SCADA master station). Since the F60 maintains two
sets of IEC 60870-5-104 data change buffers, no more than two masters should actively communicate with the F60 at one
time.
The
IEC ------- DEFAULT THRESHOLD
settings are used to determine when to trigger spontaneous responses containing
M_ME_NC_1 analog data. These settings group the F60 analog data into types: current, voltage, power, energy, and other.
Each setting represents the default threshold value for all M_ME_NC_1 analog points of that type. For example, to trigger
spontaneous responses from the F60 when any current values change by 15 A, the
IEC CURRENT DEFAULT THRESHOLD
set-
ting should be set to 15. Note that these settings are the default values of the deadbands. P_ME_NC_1 (parameter of mea-
sured value, short floating point value) points can be used to change threshold values, from the default, for each individual
M_ME_NC_1 analog point. Whenever power is removed and re-applied to the F60, the default thresholds are in effect.
The
IEC REDUNDANCY
setting decides whether multiple client connections are accepted or not. If redundancy is set to Yes,
two simultaneous connections can be active at any given time.
IEC TCP PORT NUMBER
: When set to 0, the change takes effect when the F60 is restarted.
IEC COMMON ADDRESS OF ASDU
: The change takes effect when the F60 is restarted.
IEC CYCLIC DATA PERIOD
: The change takes effect when the F60 is restarted.
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.
IEC 60870-5-104
PROTOCOL
IEC TCP PORT
NUMBER: 2404
Range: 0 to 65535 in steps of 1
MESSAGE
IEC NETWORK
CLIENT ADDRESSES
Range: see sub-menu below
MESSAGE
IEC COMMON ADDRESS
OF ASDU:
0
Range: 0 to 65535 in steps of 1
MESSAGE
IEC CYCLIC DATA
PERIOD:
60 s
Range: 1 to 65535 s in steps of 1
MESSAGE
IEC CURRENT DEFAULT
THRESHOLD: 30000
Range: 0 to 65535 in steps of 1
MESSAGE
IEC VOLTAGE DEFAULT
THRESHOLD: 30000
Range: 0 to 65535 in steps of 1
MESSAGE
IEC POWER DEFAULT
THRESHOLD: 30000
Range: 0 to 65535 in steps of 1
MESSAGE
IEC ENERGY DEFAULT
THRESHOLD: 30000
Range: 0 to 65535 in steps of 1
MESSAGE
IEC PF DEFAULT
THRESHOLD: 1.00
Range: 0.00 to 1.00
MESSAGE
IEC OTHER DEFAULT
THRESHOLD: 30000
Range: 0 to 65535 in steps of 1
MESSAGE
IEC REDUNDANCY
ENABLED: No
Range: No, Yes
NOTE
Summary of Contents for F60
Page 10: ...x F60 Feeder Protection System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 F60 Feeder Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 138: ...4 28 F60 Feeder Protection System GE Multilin 4 2 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 454: ...5 316 F60 Feeder Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 500: ...7 14 F60 Feeder Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 508: ...8 8 F60 Feeder Protection System GE Multilin 8 2 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 522: ...10 12 F60 Feeder Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 660: ...B 116 F60 Feeder Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 706: ...E 10 F60 Feeder Protection System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Page 718: ...F 12 F60 Feeder Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 728: ...H 8 F60 Feeder Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Page 730: ...H 10 F60 Feeder Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...