CHAPTER 7: COMMANDS AND TARGETS
COMMANDS MENU
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
7-3
7
COMMANDS
CLEAR RECORDS
CLEAR IEC61850 XWSI OPCNT
COMMANDS
CLEAR RECORDS
CLEAR IEC61850 XCBR OPCNT
The Clear XSWI commands clear the disconnect operation counters for each phase and the three-phase counter. Similarly,
the Clear XCBR commands clear the circuit breaker operation counters for each phase and the three-phase counter.
7.1.3 Set date and time
COMMANDS
SET DATE AND TIME
The date and time can be entered on the faceplate keypad. The time setting is based on the 24-hour clock. The complete
date, as a minimum, must be entered to allow execution of this command. The new time and date take effect when the
ENTER
key is pressed.
When the relay is synchronizing to an external time source such as PTP, IRIG-B, or SNTP, the manually entered time is over-
written.
The timescale of the entered time is local time, including daylight savings time where and when applicable.
7.1.4 Relay maintenance
COMMANDS
RELAY MAINTENANCE
This menu contains commands for relay maintenance purposes. Commands for the lamp test and order code are
activated by changing a command setting to “Yes” and pressing the
ENTER
key. The command setting then automatically
reverts to “No.” The service command is activated by entering a numerical code and pressing the
ENTER
key.
PERFORM LAMPTEST
— Turns on all faceplate LEDs and display pixels for a short duration.
UPDATE ORDER CODE
— This command causes the relay to scan the backplane for the hardware modules and update the
order code to match. If an update occurs, the following message displays.
CLEAR IEC61850
XWSI OPCNT
CLEAR XSWI 1
OpCnt? No
Range: No, Yes
CLEAR XSWI 24
OpCnt? No
Range: No, Yes
CLEAR IEC61850
XWSI OPCNT
CLEAR XCBR 1
OpCnt? No
Range: No, Yes
CLEAR XCBR 8
OpCnt? No
Range: No, Yes
COMMANDS
SET DATE AND TIME
SET DATE AND TIME:
2000/01/14 13:47:03
Range: YYYY/MM/DD HH:MM:SS
COMMANDS
RELAY MAINTENANCE
PERFORM LAMPTEST?
No
Range: No, Yes
UPDATE ORDER CODE?
No
Range: No, Yes
REBOOT RELAY?
No
Range: No, Yes
SERVICE COMMAND:
0
Range: 0, 101
SAVE VOLATILE DATA?:
No
Range: No, Yes