![GE Digital Energy L60 Instruction Manual Download Page 485](http://html.mh-extra.com/html/ge-digital-energy/l60/l60_instruction-manual_571854485.webp)
CHAPTER 6: ACTUAL VALUES
RECORDS
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
6-21
6
6.4 Records
6.4.1 Fault reports
ACTUAL VALUES
RECORDS
FAULT REPORTS
FAULT REPORT 1(15)
The latest 15 fault reports can be stored. The most recent fault location calculation (when applicable) is displayed in this
menu, along with the date and time stamp of the event which triggered the calculation. See the
SETTINGS
PRODUCT
SETUP
FAULT REPORTS
menu for assigning the source and trigger for fault calculations. See the
COMMANDS
CLEAR
RECORDS
menu for manual clearing of the fault reports and to the
SETTINGS
PRODUCT SETUP
CLEAR RELAY RECORDS
menu for automated clearing of the fault reports.
6.4.2 Event records
ACTUAL VALUES
RECORDS
EVENT RECORDS
The event records menu shows the contextual data associated with up to the last 1024 events, listed in chronological
order from most recent to oldest. When all 1024 event records have been filled, the oldest record is removed as a new
record is added. Each event record shows the event identifier/sequence number, cause, and date/time stamp associated
with the event trigger. See the
COMMANDS
CLEAR RECORDS
menu for clearing event records.
Only major output operands generate events, not every operand. Elements that assert output per phase, for example, log
operating phase output only without asserting the common three-phase operand event.
NO FAULTS TO REPORT
or
FAULT REPORT 1
FAULT 1
LINE ID: SRC 1
Range: SRC 1, SRC 2
FAULT 1 DATE:
2000/08/11
Range: YYYY/MM/DD
FAULT 1 TIME:
00:00:00.000000
Range: HH:MM:SS.ssssss
FAULT 1 TYPE:
ABG
Range: not available if the source VTs are in the
“Delta” configuration
FAULT 1 LOCATION
00.0 km
Range: not available if the source VTs are in the
“Delta” configuration
FAULT 1 RECLOSE
SHOT: 0
Range: where applicable
EVENT RECORDS
EVENT: XXXX
RESET OP(PUSHBUTTON)
Date and time stamps
EVENT: 3
POWER ON
EVENT 3
DATE: 2000/07/14
EVENT: 2
POWER OFF
EVENT 3
TIME: 14:53:00.03405
EVENT: 1
EVENTS CLEARED