5-290
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
CONTROL ELEMENTS
CHAPTER 5: SETTINGS
5
An additional condition is introduced to inhibit a fuse failure declaration when the monitored circuit is de-energized;
positive-sequence voltage and current are both below threshold levels.
VT FUSE FAILURE 1 FUNCTION
— Enables and disables the fuse failure feature for Source 1 VT Fuse Fail.
NEUTRAL WIRE OPEN 1 DETECTION
— Enables and disables the VT neutral wire open detection function. When the VT is
connected in Delta, do not enable this function because there is no neutral wire for Delta connected VT.
NEUTRAL WIRE OPEN 1 3 HRAM PKP
— Specifies the pickup level of 3rd harmonic of 3V0 signal for the
NEUTRAL WIRE OPEN
DETECTION
logic to pick up.
Base voltage for this element is
PHASE VT SECONDARY
setting in the case of WYE VTs and (
PHASE VT SECONDARY
)/
in
case
of DELTA VTs. The setting is found under
SETTINGS
SYSTEM SETUP
AC INPUTS
VOLTAGE BANK
PHASE VT SECONDARY
.
Figure 5-161: VT fuse fail logic
5.7.9.6 Open pole detector
SETTINGS
CONTROL ELEMENTS
MONITORING ELEMENTS
OPEN POLE
OPEN POLE
OPEN POLE FUNCTION:
Disabled
Range: Disabled, Enabled
OPEN POLE BLOCK:
Off
Range: FlexLogic operand
3
827093AQ.CDR
FUSE
FAIL
FAULT
AND
AND
AND
SET
RESET
Reset-dominant
Latch
AND
AND
AND
AND
OR
OR
OR
OR
Function
SETTI
N
G
Enabled = 1
SOURCE 1
V_2
V_1
I_1
Run
V_1 < 0.05 pu
Run
V_2 > 0.1 pu
Run
I_1 > 0.075 pu
Run
V_1 < 0.80 pu
Run
I_1 < 0.05 pu
SRC1 50DD OP
FLEXLOGIC OPERA
N
DS
2 cycles
20 cycles
SRC1 VT FUSE FAIL OP
FLEXLOGIC OPERA
N
DS
SRC1 VT FUSE FAIL DPO
SRC1 VT FUSE FAIL VOL LOSS
FLEXLOGIC OPERA
N
D
TIMER
OPEN POLE OP
The OPEN POLE OP operand applies
to the D60, L60, and L90
Neutral Wire Open Detect
SETTI
N
G
Enabled = 1
SOURCE 1
3V_0 (3rd Harmonic)
SETTI
N
G
Run
3V_0 3rd Harm >setting
3 HARM PKP
AND
SRC1 3V0 3nd Harmonic
FLEX-A
N
ALOG
AND
5 cycles
0
TIMER
SRC1 VT NEU WIRE OPEN
FLEXLOGIC OPERA
N
D
OR
AND
0
20 cycles
TIMER
2 cycles
0
TIMER
30 cycles
0
TIMER
COMPARATORS
VA
VB
VC
Run
|VB|-|VB| > 0.2 pu
& |VB| > 0.8 pu
Run
|VA|-|VA| > 0.2 pu
& |VA| > 0.8 pu
Run
|VC|-|VC| > 0.2 pu
& |VC| > 0.8 pu
OR
VA, VB and VC are the
voltage magnitude of one
cycle before