5-264
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
CONTROL ELEMENTS
CHAPTER 5: SETTINGS
5
GROUP 4 ACTIVATE ON
: “SELECTOR 1 POS 4"
GROUP 5 ACTIVATE ON
: “Off”
GROUP 6 ACTIVATE ON
: “Off”
Make the following changes to selector switch element in the
SETTINGS
CONTROL ELEMENTS
SELECTOR SWITCH
SELECTOR SWITCH 1
menu to assign control to user programmable pushbutton 1 and contact inputs 1 through 3:
SELECTOR 1 FUNCTION
: “Enabled”
SELECTOR 1 FULL-RANGE
: “4”
SELECTOR 1 STEP-UP MODE
: “Time-out”
SELECTOR 1 TIME-OUT
: “5.0 s”
SELECTOR 1 STEP-UP
: “PUSHBUTTON 1 ON”
SELECTOR 1 ACK
: “Off”
SELECTOR 1 3BIT A0
: “CONT IP 1 ON”
SELECTOR 1 3BIT A1
: “CONT IP 2 ON”
SELECTOR 1 3BIT A2
: “CONT IP 3 ON”
SELECTOR 1 3BIT MODE
: “Time-out”
SELECTOR 1 3BIT ACK
: “Off”
SELECTOR 1 POWER-UP MODE
: “Synchronize”
Now, assign the contact output operation (assume the H6E module) to the selector switch element by making the following
changes in the
SETTINGS
INPUTS/OUTPUTS
CONTACT OUTPUTS
menu:
OUTPUT H1 OPERATE
: “SELECTOR 1 BIT 0"
OUTPUT H2 OPERATE
: “SELECTOR 1 BIT 1"
OUTPUT H3 OPERATE
: “SELECTOR 1 BIT 2"
Finally, assign configure user-programmable pushbutton 1 by making the following changes in the
SETTINGS
PRODUCT
SETUP
USER-PROGRAMMABLE PUSHBUTTONS
USER PUSHBUTTON 1
menu:
PUSHBUTTON 1 FUNCTION
: “Self-reset”
PUSHBUTTON 1 DROP-OUT TIME
: “0.10 s”
The figure shows the logic for the selector switch.
Figure 5-149: Selector switch logic
842012A2.CDR
step up
acknowledge
3-bit position out
ON
FLEXLOGIC™ OPERANDS
SELECTOR 1 POS 1
SELECTOR 1 POS 2
SELECTOR 1 POS 3
SELECTOR 1 POS 4
SELECTOR 1 POS 5
SELECTOR 1 POS 6
SELECTOR 1 POS 7
SELECTOR 1 STP ALARM
SELECTOR 1 BIT ALARM
SELECTOR 1 ALARM
SELECTOR 1 BIT 0
SELECTOR 1 BIT 1
SELECTOR 1 BIT 2
FLEXLOGIC™ OPERANDS
RUN
SELECTOR 1 POWER-UP MODE:
SETTINGS
SELECTOR 1 TIME-OUT:
SELECTOR 1 STEP-UP MODE:
SELECTOR 1 FULL RANGE:
SELECTOR 1 STEP-UP:
Off = 0
SELECTOR 1 FUNCTION:
SETTINGS
Enabled = 1
SELECTOR 1 ACK:
Off = 0
SELECTOR 1 3BIT A0:
Off = 0
SELECTOR 1 3BIT A1:
Off = 0
SELECTOR 1 3BIT A2:
Off = 0
SELECTOR 1 3BIT ACK:
Off = 0
3-bit acknowledge
SELECTOR 1 POSITION
ACTUAL VALUE
2
1
3
4
5
6
7
SELECTOR 1 3BIT MODE:
SELECTOR 1 PWR ALARM
thr
ee-bit
contr
ol
input
OR