5-258
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
CONTROL ELEMENTS
CHAPTER 5: SETTINGS
5
Figure 5-145: Trip bus logic
5.7.3 Setting groups
SETTINGS
CONTROL ELEMENTS
SETTING GROUPS
The setting groups menu controls the activation and deactivation of up to six possible groups of settings in the
GROUPED
ELEMENTS
settings menu. The active setting group can be indicated on the front display of the UR by configuring User-
Programmable LEDs to display the state of the
SETTING GROUP ACT
FlexLogic operands.
SETTING GROUPS FUNCTION
— When Enabled, allows setting groups other than group 1 (the default active group) to be
activated. The default setting group is forced active while the
SETTING GROUPS FUNCTION
setting is Disabled.
SETTING GROUPS BLK —
Prevents the active setting group from changing when the selected FlexLogic operand is "On." This
can be useful in applications where it is undesirable to change the settings under certain conditions, such as during a
control sequence.
SETTING GROUPS
SETTING GROUPS
FUNCTION: Enabled
Range: Disabled, Enabled
SETTING GROUPS BLK:
Off
Range: FlexLogic operand
GROUP 2 ACTIVATE ON:
Off
Range: FlexLogic operand
GROUP 6 ACTIVATE ON:
Off
Range: FlexLogic operand
GROUP 1 NAME:
Range: up to 16 alphanumeric characters
GROUP 6 NAME:
Range: up to 16 alphanumeric characters
SETTING GROUP
EVENTS: Disabled
Range: Disabled, Enabled
***
SETTINGS
= Off
TRIP BUS 1 INPUT 2
= Off
TRIP BUS 1 INPUT 1
= Off
TRIP BUS 1 INPUT 16
OR
SETTINGS
= Enabled
TRIP BUS 1
FUNCTION
= Off
TRIP BUS 1 BLOCK
AND
AND
Latch
S
R
Non-volatile,
set-dominant
SETTINGS
= Enabled
TRIP BUS 1
LATCHING
= Off
TRIP BUS 1 RESET
FLEXLOGIC OPERAND
TRIP BUS 1 PKP
OR
SETTINGS
TRIP BUS 1 PICKUP
DELAY
TRIP BUS 1 RESET
DELAY
T
PKP
T
RST
FLEXLOGIC OPERAND
RESET OP
FLEXLOGIC OPERAND
TRIP BUS 1 OP
842023A1.CDR