CHAPTER 5: SETTINGS
GROUPED ELEMENTS
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
5-255
5
Figure 5-142: Auxiliary undervoltage logic
5.6.14.7 Auxiliary overvoltage (ANSI 59X, IEC PTOV)
SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
VOLTAGE ELEMENTS
AUXILIARY OV1(2)
The L60 contains one auxiliary overvoltage element for each VT bank. This element is intended for monitoring overvoltage
conditions of the auxiliary voltage. The nominal secondary voltage of the auxiliary voltage channel entered under
SYSTEM
SETUP
AC INPUTS
VOLTAGE BANK X5
AUXILIARY VT X5 SECONDARY
is the per-unit (pu) base used when setting the
pickup level.
A typical application for this element is monitoring the zero-sequence voltage (3V_0) supplied from an open-corner-delta
VT connection.
AUXILIARY OV1
AUX OV1
FUNCTION: Disabled
Range: Disabled, Enabled
AUX OV1 SIGNAL
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
AUX OV1 PICKUP:
0.300 pu
Range: 0.000 to 3.000 pu in steps of 0.001
AUX OV1 PICKUP
DELAY: 1.00 s
Range: 0.00 to 600.00 s in steps of 0.01
AUX OV1 RESET
DELAY: 1.00 s
Range: 0.00 to 600.00 s in steps of 0.01
AUX OV1 BLOCK:
Off
Range: FlexLogic operand
AUX OV1 TARGET:
Self-reset
Range: Self-reset, Latched, Disabled
AUX OV1 EVENTS:
Disabled
Range: Disabled, Enabled
827849A3.CDR
FLEXLOGIC OPERANDS
AUX UV1
FUNCTION:
AUX UV1 BLOCK:
AUX UV1 SIGNAL
SOURCE:
AUX UV1 MINIMUM
VOLTAGE:
AUX UV1 DPO
AUX UV1 OP
AUX UV1 PKP
RUN
SETTING
SETTING
AUX UV1 CURVE:
AUX UV1 DELAY:
AUX UV1 PICKUP:
SETTING
Enabled=1
SETTING
SETTING
Off=0
AUX VOLT Vx
Vx Minimum
Vx Pickup
t
V
<
<
AND