CHAPTER 5: SETTINGS
GROUPED ELEMENTS
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
5-215
5
Figure 5-115: Phase time overcurrent 1 logic
5.6.8.4 Phase instantaneous overcurrent (ANSI 50P, IEC PIOC)
SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
PHASE CURRENT
PHASE IOC 1(4)
PHASE IOC 1
PHASE IOC1
FUNCTION: Disabled
Range: Disabled, Enabled
PHASE IOC1 SIGNAL
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
PHASE IOC1
PICKUP: 1.000 pu
Range: 0.000 to 30.000 pu in steps of 0.001
PHASE IOC1 PICKUP
DELAY: 0.00 s
Range: 0.00 to 600.00 s in steps of 0.01
PHASE IOC1 RESET
DELAY: 0.00 s
Range: 0.00 to 600.00 s in steps of 0.01
PHASE IOC1 BLOCK A:
Off
Range: FlexLogic operand
PHASE IOC1 BLOCK C:
Off
Range: FlexLogic operand
PHASE IOC1
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
PHASE IOC1
EVENTS: Disabled
Range: Disabled, Enabled
SETTING
SETTING
SETTING
SETTING
SETTING
MULTIPLY INPUTS
FLEXLOGIC OPERAND
SETTING
PHASE TOC1
FUNCTION:
PHASE TOC1
BLOCK-A :
PHASE TOC1
BLOCK-C:
PHASE TOC1
BLOCK-B:
PHASE TOC1 VOLT
RESTRAINT:
PHASE TOC1 A PKP
PHASE TOC1 A DPO
PHASE TOC1 A OP
PHASE TOC1 B PKP
PHASE TOC1 B DPO
PHASE TOC1 B OP
PHASE TOC1 C PKP
PHASE TOC1 C DPO
PHASE TOC1 C OP
PHASE TOC1 PKP
PHASE TOC1 OP
PHASE TOC1
SOURCE:
PHASE TOC1
RESET:
PHASE TOC1
CURVE:
PHASE TOC1
PICKUP:
PHASE TOC1
INPUT:
IA
Seq=ABC Seq=ACB
Set
Multiplier
Set
Multiplier
Set
Multiplier
Set Pickup
Multiplier-Phase A
Calculate
Calculate
Calculate
Set Pickup
Multiplier-Phase B
Set Pickup
Multiplier-Phase C
RUN
IB
VAB
VAC
RUN
IC
VBC
VBA
VCA
VCB
RUN
Off=0
Off=0
Off=0
Enabled
Enabled=1
OR
AND
AND
AND
OR
827072A5.CDR
PHASE TOC1
TD MULTIPLIER:
RUN
RUN
RUN
IA
PICKUP
t
t
t
IB
PICKUP
IC
PICKUP
SETTING
PHASE TOC1 DPO
AND