![GE Digital Energy L60 Instruction Manual Download Page 27](http://html.mh-extra.com/html/ge-digital-energy/l60/l60_instruction-manual_571854027.webp)
CHAPTER 2: PRODUCT DESCRIPTION
SPECIFICATIONS
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
2-17
2
Voltage supervision pickup (series compensation applications):
0 to 5.000 pu in steps of 0.001
Operation time:
1 to 1.5 cycles (typical)
Reset time:
1 power cycle (typical)
GROUND DISTANCE
Characteristic:
Mho (memory polarized or offset) or Quad (memory polarized or non-directional)
Reactance polarization:
negative-sequence or zero-sequence current
Non-homogeneity angle:
–40 to 40° in steps of 1
Number of zones:
3
Directionality:
forward, reverse, or non-directional
Reach (secondary
Ω
):
0.02 to 500.00
Ω
in steps of 0.01
Reach accuracy:
±5% including the effect of CVT transients up to an SIR of 30
Distance characteristic angle:
30 to 90° in steps of 1
Distance comparator limit angle:
30 to 90° in steps of 1
Directional supervision:
Characteristic angle:
30 to 90° in steps of 1
Limit angle:
30 to 90° in steps of 1
Zero-sequence compensation
Z0/Z1 magnitude:
0.00 to 10.00 in steps of 0.01
Z0/Z1 angle:
–90 to 90° in steps of 1
Zero-sequence mutual compensation
Z0M/Z1 magnitude:
0.00 to 7.00 in steps of 0.01
Z0M/Z1 angle:
–90 to 90° in steps of 1
Right blinder (Quad only):
Reach:
0.02 to 500
Ω
in steps of 0.01
Characteristic angle:
60 to 90° in steps of 1
Left blinder (Quad only):
Reach:
0.02 to 500
Ω
in steps of 0.01
Characteristic angle:
60 to 90° in steps of 1
Time delay:
0.000 to 65.535 s in steps of 0.001
Timer accuracy:
±3% of operate time or ±1/4 cycle (whichever is greater)
Current supervision:
Level:
neutral current (3I_0)
Pickup:
0.050 to 30.000 pu in steps of 0.001
Dropout:
97 to 98%
Memory duration:
5 to 25 cycles in steps of 1
Voltage supervision pickup (series compensation applications):
0 to 5.000 pu in steps of 0.001
Operation time:
1 to 1.5 cycles (typical)
Reset time:
1 power cycle (typical)
LINE PICKUP
Phase instantaneous overcurrent:
0.000 to 30.000 pu
Undervoltage pickup:
0.000 to 3.000 pu
Overvoltage delay:
0.000 to 65.535 s
PHASE/NEUTRAL/GROUND TOC
Current:
Phasor or RMS
Pickup level:
0.000 to 30.000 pu in steps of 0.001
Dropout level:
97% to 98% of pickup
Level accuracy:
0.1 to 2.0
×
CT:
±0.5% of reading or ±0.4% of rated (whichever is greater)
> 2.0
×
CT:
±1.5% of reading > 2.0
×
CT rating
Curve shapes:
IEEE Moderately/Very/Extremely Inverse; IEC (and BS) A/B/C and Short Inverse; GE IAC Inverse,
Short/Very/ Extremely Inverse; I
2
t; FlexCurves™ (programmable); Definite Time (0.01 s base
curve)