CHAPTER 5: SETTINGS
PRODUCT SETUP
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
5-21
5
•
Observer — This role has read-only access to all L60 settings. This role allows unlimited concurrent access but it has
no download access to any files on the device. Observer is the default role if no authentication has been done to the
device. This role displays as "None" on the front panel.
Change local passwords
SETTINGS
PRODUCT SETUP
SECURITY
CHANGE LOCAL PASSWORDS
The Change Local Passwords menu is shown on the front panel and in EnerVista upon successful login of the Administrator
role.
The
LOGIN
setting in this menu is similar to that described in
SETTINGS > PRODUCT SETUP > SECURITY
except for the factory
role.
Passwords are stored in text format. No encryption is applied.
Session settings
SETTINGS
PRODUCT SETUP
SECURITY
SESSION SETTINGS
SESSION LOCKOUT
— This setting specifies the number of failed authentications before the device blocks subsequent
authentication attempts for the lockout period. A value of zero means lockout is disabled.
SESSION LOCKOUT PERIOD
— This setting specifies the period of time in minutes of a lockout period. A value of 0 means that
there is no lockout period.
Restore defaults
SETTINGS
PRODUCT SETUP
SECURITY
RESTORE DEFAULTS
NOTE
The Factory service role is not available. It is for factory use only.
CHANGE LOCAL
PASSWORDS
LOGIN:
None
Range: 20 alphanumeric characters
NEW PASSWORD:
Range: 20 alphanumeric characters
CONFIRM PASSWORD:
Range: 20 alphanumeric characters
NOTE
In Device authentication mode, the Observer role does not have a password associated with it. In Server
authentication mode the Observer role requires a password.
If you are locked out of the software, contact GE Digital Energy for the default password. When using
CyberSentry, the default password is "ChangeMe1#".
Once the passwords are set, the Administrator with Supervisor approval can change the role-associated
password.
In CyberSentry, password encryption is not supported.
SESSION
SETTINGS
SESSION LOCKOUT:
3
Range: 0 to 99
SESSION LOCKOUT
PERIOD: 3 min
Range: 0 to 9999 minutes
RESTORE DEFAULTS
LOAD FACTORY
DEFAULTS: No
Range: Yes, No