B.4 MEMORY MAPPING
APPENDIX B
B
B.4.2 DATA FORMATS
F001
UR_UINT16 UNSIGNED 16 BIT INTEGER
F002
UR_SINT16 SIGNED 16 BIT INTEGER
F003
UR_UINT32 UNSIGNED 32 BIT INTEGER (2 registers)
High order word is stored in the first register.
Low order word is stored in the second register.
F004
UR_SINT32 SIGNED 32 BIT INTEGER (2 registers)
High order word is stored in the first register/
Low order word is stored in the second register.
F005
UR_UINT8 UNSIGNED 8 BIT INTEGER
F006
UR_SINT8 SIGNED 8 BIT INTEGER
F011
UR_UINT16 FLEXCURVE DATA (120 points)
A FlexCurve is an array of 120 consecutive data points (x, y) which
are interpolated to generate a smooth curve. The y-axis is the user
defined trip or operation time setting; the x-axis is the pickup ratio
and is pre-defined. Refer to format F119 for a listing of the pickup
ratios; the enumeration value for the pickup ratio indicates the off-
set into the FlexCurve base address where the corresponding time
value is stored.
F012
DISPLAY_SCALE DISPLAY SCALING
(unsigned 16-bit integer)
MSB indicates the SI units as a power of ten. LSB indicates the
number of decimal points to display.
Example: Current values are stored as 32 bit numbers with three
decimal places and base units in Amps. If the retrieved value is
12345.678 A and the display scale equals 0x0302 then the dis-
played value on the unit is 12.35 kA.
F013
POWER_FACTOR (SIGNED 16 BIT INTEGER)
Positive values indicate lagging power factor; negative values
indicate leading.
F040
UR_UINT48 48-BIT UNSIGNED INTEGER
F050
UR_UINT32 TIME and DATE (UNSIGNED 32 BIT INTEGER)
Gives the current time in seconds elapsed since 00:00:00 January
1, 1970.
F051
UR_UINT32 DATE in SR format (alternate format for F050)
First 16 bits are Month/Day (MM/DD/xxxx). Month: 1=January,
2=February,...,12=December; Day: 1 to 31 in steps of 1
Last 16 bits are Year (xx/xx/YYYY): 1970 to 2106 in steps of 1
F052
UR_UINT32 TIME in SR format (alternate format for F050)
First 16 bits are Hours/Minutes (HH:MM:xx.xxx).
Hours: 0=12am, 1=1am,...,12=12pm,...23=11pm;
Minutes: 0 to 59 in steps of 1
Last 16 bits are Seconds (xx:xx:.SS.SSS): 0=00.000s,
1=00.001,...,59999=59.999s)
F060
FLOATING_POINT IEEE FLOATING POINT (32 bits)
F070
HEX2 2 BYTES - 4 ASCII DIGITS
F071
HEX4 4 BYTES - 8 ASCII DIGITS
F072
HEX6 6 BYTES - 12 ASCII DIGITS
F073
HEX8 8 BYTES - 16 ASCII DIGITS
F074
HEX20 20 BYTES - 40 ASCII DIGITS
F080
ENUMERATION: AUTORECLOSE MODE
0 = 1 & 3 Pole, 1 = 1 Pole, 2 = 3 Pole-A, 3 = 3 Pole-B
F083
ENUMERATION: SELECTOR MODES
0 = Time-Out, 1 = Acknowledge
Summary of Contents for L30
Page 10: ...x L30 Line Current Differential System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 L30 Line Current Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 370: ...5 244 L30 Line Current Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 464: ...A 10 L30 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 600: ...C 30 L30 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 610: ...D 10 L30 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 622: ...E 12 L30 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 634: ...F 12 L30 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 644: ...x L30 Line Current Differential System GE Multilin INDEX ...