6-24
L30 Line Current Differential System
GE Multilin
6.4 RECORDS
6 ACTUAL VALUES
6
PATH: ACTUAL VALUES
RECORDS
PMU RECORDS
PMU 1 RECORDING
6.4.6 BREAKER MAINTENANCE
PATH: ACTUAL VALUES
RECORDS
MAINTENANCE
BREAKER 1(2)
There is an identical menu for each of the breakers. The
BKR 1 ARCING AMP
values are in units of kA
2
-cycles. Refer to the
COMMANDS
CLEAR RECORDS
menu for clearing breaker arcing current records. The
BREAKER OPERATING TIME
is
defined as the slowest operating time of breaker poles that were initiated to open.
PMU 1
RECORDING
PMU 1 FORCE TRIGGER:
Yes
Range: No, Yes
MESSAGE
PUM 1 AVAILABLE
RECORDS: 0
Range: 0 to 65535 in steps of 1
MESSAGE
PUM 1 SECONDS
PER RECORD: 0.0
Range: 0 to 6553.5 in steps of 0.1
MESSAGE
PUM 1 LAST CLEARED:
2005/07/14 015:40:16
Range: date and time in format shown
BREAKER 1
BKR 1 ARCING AMP
A:
0.00 kA2-cyc
MESSAGE
BKR 1 ARCING AMP
B:
0.00 kA2-cyc
MESSAGE
BKR 1 ARCING AMP
C:
0.00 kA2-cyc
MESSAGE
BKR 1 OPERATING TIME
A: 0
ms
MESSAGE
BKR 1 OPERATING TIME
B: 0
ms
MESSAGE
BKR 1 OPERATING TIME
C: 0
ms
MESSAGE
BKR 1 OPERATING
TIME:
0 ms
Summary of Contents for L30
Page 10: ...x L30 Line Current Differential System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 L30 Line Current Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 370: ...5 244 L30 Line Current Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 464: ...A 10 L30 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 600: ...C 30 L30 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 610: ...D 10 L30 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 622: ...E 12 L30 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 634: ...F 12 L30 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 644: ...x L30 Line Current Differential System GE Multilin INDEX ...