2-12
B90 Low Impedance Bus Differential System
GE Multilin
2.3 SPECIFICATIONS
2 PRODUCT DESCRIPTION
2
2.3SPECIFICATIONS
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE
2.3.1 PROTECTION ELEMENTS
The operating times include the activation time of a trip rated form-A output contact unless otherwise indicated.
FlexLogic operands of a given element are 4 ms faster. Take this into account when using FlexLogic to interconnect
with other protection or control elements of the relay, building FlexLogic equations, or interfacing with other IEDs or
power system devices via communications or different output contacts. If not specified, the operate times given
here are for a 60 Hz system at nominal system frequency. Operate times for a 50 Hz system are 1.2 times longer.
BUS DIFFERENTIAL (87B)
Pickup level:
0.050 to 6.000 pu in steps of 0.001
Low slope:
15 to 100% in steps of 1
High slope:
50 to 100% in steps of 1
Low breakpoint:
1.00 to 30.00 pu in steps of 0.01
High breakpoint:
1.00 to 30.00 pu in steps of 0.01
High set level:
0.10 to 99.99 pu in steps of 0.01
Dropout level:
97 to 98% of pickup
Level accuracy:
0.1 to 2.0
CT rating: ±0.5% of reading or ±1% of rated (which-
ever is greater)
>2.0
CT rating
±1.5% of reading
Operating time:
one power system cycle (typical)
Number of zones:
1 or 4 (option)
Max number of inputs:
8, 16, or 24 (option)
CT TROUBLE
Responding to:
Differential current
Pickup level:
0.020 to 2.000 pu in steps of 0.001
Pickup delay:
1.0 to 60.0 sec. in steps of 0.1
Timer accuracy:
±3% of operate time or ±1/4 cycle
(whichever is greater)
Availability:
one per zone of protection
ISOLATOR MONITORING
Responding to:
Both normally-open and normally-closed
auxiliary contacts
Asserting:
Isolator Position, Isolator Alarm, Block
Switching
Alarm pickup delay:
0.00 to 120.00 s in steps of 0.05
Timer accuracy:
±3% of operate time or ±1/4 cycle
(whichever is greater)
TIME OVERCURRENT
Pickup level:
0.000 to 30.000 pu in steps of 0.001
Dropout level:
97 to 98% of pickup
Level accuracy:
0.1 to 2.0
CT
0.5% of reading or 1% of nominal
(whichever is greater)
above 2.0
CT
1.5% of reading
Curve shapes:
IEEE Moderately/Very/Extremely
Inverse; IEC (and BS) A/B/C and Short
Inverse; GE IAC Inverse, Short/Very/
Extremely Inverse; I
2
t; FlexCurves™
(programmable); Definite Time (0.01 s
base curve)
TD multiplier:
0.00 to 600.00 in steps of 0.01
Reset type:
Instantaneous or Timed (per IEEE)
Curve timing accuracy
at 1.03 to 20 x pickup:
±3.5% of operate time or ±1/2 cycle
(whichever is greater) from pickup to
operate
INSTANTANEOUS OVERCURRENT
Pickup level:
0.000 to 30.000 pu in steps of 0.001
Dropout level:
97 to 98% of pickup
Level accuracy:
0.1 to 2.0
CT
0.5% of reading or 1% of nominal
(whichever is greater)
above 2.0
CT
1.5% of reading
Pickup delay:
0 to 65.535 s in steps of 0.001
Reset delay:
0 to 65.535 s in steps of 0.001
Timer accuracy:
±3% of operate time or ±1/4 cycle
(whichever is greater)
Operate time:
16 ms at 3x pickup at 60 Hz
UNDERVOLTAGE
Pickup level:
0.000 to 3.000 pu in steps of 0.001
Dropout level:
102 to 103% of pickup
Level accuracy:
±0.5% of reading from 10 to 208 V
Pickup delay:
0 to 65.535 s in steps of 0.001
Reset delay:
0 to 65.535 s in steps of 0.001
Timer accuracy:
±3% of operate time or ±1/4 cycle
(whichever is greater)
Operate time:
16 ms at <0.9 x pickup at 60 Hz
END FAULT PROTECTION
IOC pickup level:
0.000 to 30.000 pu in steps of 0.001
IOC dropout level:
97 to 98% of pickup
Level accuracy
at 0.1 to 2.0
CT:
0.5% of reading or 1% of nominal
(whichever is greater)
above 2.0
CT:
1.5% of reading
CB open pickup timer:
0 to 65.535 s in steps of 0.001
End Fault pickup timer: 0 to 65.535 s in steps of 0.001
Timer accuracy:
±3% of operate time or ±8 ms, whichever
is greater
BREAKER FAILURE
Mode:
3-pole
Current supervision:
phase current
Current supv. pickup:
0.001 to 30.000 pu in steps of 0.001
Current supv. dropout:
97 to 98% of pickup
Current supv. accuracy:
0.1 to 2.0
CT rating: ±0.75% of reading or ±2% of rated
(whichever is greater)
NOTE
Summary of Contents for B90
Page 10: ...x B90 Low Impedance Bus Differential System GE Multilin TABLE OF CONTENTS ...
Page 284: ...5 166 B90 Low Impedance Bus Differential System GE Multilin 5 8 TESTING 5 SETTINGS 5 ...
Page 334: ...10 8 B90 Low Impedance Bus Differential System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Page 338: ...A 4 B90 Low Impedance Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 460: ...C 30 B90 Low Impedance Bus Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 476: ...E 10 B90 Low Impedance Bus Differential System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Page 502: ...viii B90 Low Impedance Bus Differential System GE Multilin INDEX ...