5-128
B90 Low Impedance Bus Differential System
GE Multilin
5.5 GROUPED ELEMENTS
5 SETTINGS
5
b) INVERSE TOC CURVE CHARACTERISTICS
The inverse time overcurrent curves used by the time overcurrent elements are the IEEE, IEC, GE Type IAC, and I
2
t stan-
dard curve shapes. This allows for simplified coordination with downstream devices.
A time dial multiplier setting allows selection of a multiple of the base curve shape (where the time dial multiplier = 1) with
the curve shape (
CURVE
) setting. Unlike the electromechanical time dial equivalent, operate times are directly proportional
to the time multiplier (
TD MULTIPLIER
) setting value. For example, all times for a multiplier of 10 are 10 times the multiplier 1
or base curve values. Setting the multiplier to zero results in an instantaneous response to all current levels above pickup.
Time overcurrent time calculations are made with an internal
energy capacity
memory variable. When this variable indi-
cates that the energy capacity has reached 100%, a time overcurrent element will operate. If less than 100% energy capac-
ity is accumulated in this variable and the current falls below the dropout threshold of 97 to 98% of the pickup value, the
variable must be reduced. Two methods of this resetting operation are available: “Instantaneous” and “Timed”. The “Instan-
taneous” selection is intended for applications with other relays, such as most static relays, which set the energy capacity
directly to zero when the current falls below the reset threshold. The “Timed” selection can be used where the relay must
coordinate with electromechanical relays.
IEEE CURVES:
The IEEE time overcurrent curve shapes conform to industry standards and the IEEE C37.112-1996 curve classifications
for extremely, very, and moderately inverse. The IEEE curves are derived from the formulae:
,
(EQ 5.5)
where:
T
= operate time (in seconds),
TDM
= Multiplier setting,
I
= input current,
I
pickup
= Pickup Current setting
A
,
B
,
p
= constants,
T
RESET
= reset time in seconds (assuming energy capacity is 100% and
RESET
is “Timed”),
t
r
= characteristic constant
Table 5–16: OVERCURRENT CURVE TYPES
IEEE
IEC
GE TYPE IAC
OTHER
IEEE Extremely Inverse
IEC Curve A (BS142)
IAC Extremely Inverse
I
2
t
IEEE Very Inverse
IEC Curve B (BS142)
IAC Very Inverse
Definite Time
IEEE Moderately Inverse
IEC Curve C (BS142)
IAC Inverse
IEC Short Inverse
IAC Short Inverse
Table 5–17: IEEE INVERSE TIME CURVE CONSTANTS
IEEE CURVE SHAPE
A
B
P
T
R
IEEE Extremely Inverse
28.2
0.1217
2.0000
29.1
IEEE Very Inverse
19.61
0.491
2.0000
21.6
IEEE Moderately Inverse
0.0515
0.1140
0.02000
4.85
Table 5–18: IEEE CURVE TRIP TIMES (IN SECONDS)
MULTIPLIER
(TDM)
CURRENT (
I
/
I
pickup
)
1.5
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
IEEE EXTREMELY INVERSE
0.5
11.341
4.761
1.823
1.001
0.648
0.464
0.355
0.285
0.237
0.203
1.0
22.682
9.522
3.647
2.002
1.297
0.927
0.709
0.569
0.474
0.407
2.0
45.363
19.043
7.293
4.003
2.593
1.855
1.418
1.139
0.948
0.813
4.0
90.727
38.087
14.587
8.007
5.187
3.710
2.837
2.277
1.897
1.626
6.0
136.090
57.130
21.880
12.010
7.780
5.564
4.255
3.416
2.845
2.439
8.0
181.454
76.174
29.174
16.014
10.374
7.419
5.674
4.555
3.794
3.252
10.0
226.817
95.217
36.467
20.017
12.967
9.274
7.092
5.693
4.742
4.065
IEEE VERY INVERSE
T
TDM
A
I
I
pickup
----------------
p
1
–
----------------------------------
B
+
=
T
RESET
TDM
t
r
1
I
I
pickup
----------------
2
–
------------------------------------
=
Summary of Contents for B90
Page 10: ...x B90 Low Impedance Bus Differential System GE Multilin TABLE OF CONTENTS ...
Page 284: ...5 166 B90 Low Impedance Bus Differential System GE Multilin 5 8 TESTING 5 SETTINGS 5 ...
Page 334: ...10 8 B90 Low Impedance Bus Differential System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Page 338: ...A 4 B90 Low Impedance Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 460: ...C 30 B90 Low Impedance Bus Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 476: ...E 10 B90 Low Impedance Bus Differential System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Page 502: ...viii B90 Low Impedance Bus Differential System GE Multilin INDEX ...