GASMAX II Operation & Maintenance Manual, Revision 7.0
Page 38
Figure 7-7: Clock Delay Menu
TIME
adjusts time of day in hours, minutes and seconds.
DATE
adjusts date in month, day, year.
WARM UP DELAY
sets the amount of time from power-on until the 4-20mA output signal begins to
track the sensor output. Default setting is 60 seconds. Maximum value is 255 seconds.
CAL PURGE DELAY
sets the amount of time from the completion of span calibration until the 4-20mA
output signal restarts tracking the sensor output. The default setting is 60 seconds and the maximum
value is 255 seconds.
LCD CONTRAST ADJUSTMENT PAGE
The LCD Contrast Adjustment allows the display to be set for optimum viewing.
Figure 7-8: Contrast Menu
HELP SCREEN PAGE
The Help screen contains several pages of information describing GASMAX II operation.
DIAGNOSTICS PAGE
The Diagnostics page provides tools for use during setup or testing. Since relays are not available on the
GASMAX II, the Relay Test option is not functional.
Figure 7-9: Diagnostics Menu
C L OC K / D E L A Y S E T U P
T i me 12 : 3 5 : 4 2
D a t e 0 4 / 2 2 / 0 4
Wa r m U p S e c 12 0
C a l P u r g e S e c 10 0
C ON T R A S T
U P / D OWN t o c h a n g e
N E X T t o E X I T
* * * WA R N I N G * * *
A l a r m p r o c e s s i n g w i l l
b e h a l t e d d u r i n g
d i a g n o s t i c mo d e !
E D I T t o c o n t i n u e .
A n y o t h e r k e y t o e x i t .
D I A GN OS T I C S
Ou t p u t S t i mu l a t i o n
R e l a y T e s t
OU T P U T S T I MU L A T OR
Ou t p u t 4 . 0 mA
E D I T t o c h a n g e .
N e x t t o e x i t .
EDIT
A C T I V A T E R E L A Y S
R e l a y 1 OF F
R e l a y 2 OF F
R e l a y 3 OF F