GDS GASMAX II Quick Start Manual Download Page 1

AUTHORIZED DISTRIBUTOR -  GasDetectorsUSA.com -  Houston, Texas USA

Quickstart Guide  

GASMAX II Gas Monitor with Remote  

SmartIR Combustible Gas Sensor 

[email protected] 

IMPORTANT

 - 

Before installing the GASMAX II, 

make sure no toxic or combustible gases are 

present. Declassify the area if necessary. 

 

Air movement by fans, wind, gas density, 

convection, emission sources and environmental 

variables should be taken into account when 

determining location. As with all sensors, the 

GASMAX II should be protected from falling or 

directed water, snow, shock, vibration and dirt. 

Use installation practices approved for the 

appropriate area classification. When installed with 

#10-0247 Stainless Steel sensor head, the 

GASMAX II is certified for use in areas rated Class 

1, Div 1, Groups B, C & D.  

Access the GASMAX II display assembly by 

opening the explosion-proof cover and loosening 

INSTALLATION 

WIRING & INITIAL SETUP 

CALIBRATION 

After warm-up, follow the on-screen instructions to 

calibrate the unit. When calibration is complete, the 

GASMAX II will indicate CAL DELAY and then resume 

normal operation. 

GASMAX II Power Supply Board  

the two thumbscrews. The power supply board is 

attached to the rear of the enclosure.  

Connect the GASMAX and remote sensor as shown 

using shielded cable. Ground the shield on one end 

only. Reinstall the GASMAX II display and cover.  

Apply power and allow the instrument to warm up for a 

minimum of one (1) hour. Readjust the sensor voltage to 

4.5VDC 

as measured at the sensor junction box

 across 

pins “R” and “A”.  

Perform a balance adjustment as described in the 

GASMAX manual.  

TB1 

TB2 

S1 

TP1 

P

W

R

 

O

U

T

 4

-2

0

 

“E

C

H

E

M

” 

O

U

T

 4

-2

0

  

“L

E

L

” 

G

N

D

 

GASM AX  I/O  Po wer 

Sup ply P/N  10-0 23 3 

C

O

M

 

A

C

T

 

R

E

F

 

“CA TBEA D” 

C1 

C2 

C8 

C7 

S1 

TB2 

TB1 

SW1 

A  

A  

Remote SmartIR Sensor Assembly  

Important: 

 

Do NOT exceed 5.5V across remote sensor 

terminals R & A with the sensor in place.   

If moisture is present, do not install remote 

sensor with unused inlet facing up. 

-  832-615-3588