GASMAX II + GDS-IR Operation & Maintenance Manual, Revision 1.1
Page 31
CAL Mode until the correct Pass Code is entered. LOW and HIGH security levels always allow static
viewing of configuration menus.
TECHNICIANS MENU GROUP
The TECHNICIANS MENU group consists of the XMITTER CONFIG menu and TECHNICAL PAGE menu. These
menus contain items that are typically factory configured depending upon the type sensor and input
connected. Care should be used when modifying these variables as some items will prevent proper
operation and could endanger personnel.
Access requires a special key sequence of four UP keystrokes to prevent accidental modification of critical
items.
XMITTER CONFIG MENU
The XMITTER CONFIG menu is used to activate channels, precisely calibrate 4-20mA outputs and set time
/ date. To access the XMITTER CONFIG menu, press and hold the NEXT key for 5-seconds until the screen
appears requesting the special key sequence.
WARNING
: TARGET GAS MONITORING AND ALARM PROCESSING ARE NOT ACTIVE WHILE IN THIS MENU.
Figure 7-11: Xmitter Config Menu
O2 / TOXIC
when set to YES enables the Oxygen / Toxic channel (Channel 1).
LEL / CURRENT
when set to YES enables the LEL / Current channel (Channel 2).
OUTPUT ZERO / SPAN TRIM
provides a way to precisely set the GASMAX II 4mA and 20mA outputs to
compensate for variation in output components. These settings are programmed at the factory and
should not be modified.
REAL TIME CLOCK
adjusts the date and time for use in EVENT LOGGING. The current time and date can
also be adjusted from the Main Menu (See Section 7).
X M I T T E R
C O N F I G
O 2 / T O X I C
O N
L E L / C U R R E N T
O N
O u t p u t
Z e r o
O u t p u t
S p a n
R e a l
T i m e
C l o c k
M o d e l
S T - 4 8
B a c k L i g h t
O N
>
>
>
E n t e r
K e y
S e q u e n c e
t o
a c c e s s
m e n u .
* * * *
N E X T
k e y
t o
E x i t .
S e e
M a n u a l
/
H E L P
P R E S S
U P K E Y
4 - T IM E S
H O L D
N E X T K E Y
5 - S E C O N D S