CHV Mini VRF 50/60Hz
4. Electric Wiring Installations
4.1 Outdoor unit wiring
Power line of outdoorunit
Junctionbox
Power line of indoorunit
Outdoorunit
Indoorunit
Indoorunit
Indoorunit
Centralized
controller CCM
Powersupply
Powersupply
Switch / powersupply
Switch / powersupply
Capacity (kW)
Power Supply
Power Line
(mm2)
Breaker/Fuse (A)
Signal Wire between Indoor and Outdoor
Units (mm)
8/10
220-240V 50Hz/60Hz
3
×
4.0
40/30
three-core shielded cable 3
×
1.0
(two-core shielded cable 2
×
1.0)
12.5/14/16
220-240V 50Hz/60Hz
3
×
6.0
63/45
12.5/14/16
380-415V 50Hz/60Hz
5
×
2.5
25/20
Communicationwire
X
Y E
P Q
E
Indoor unit
Outdoor unit
Y/G
L N
Three-core
shielded cable
Three-core shielded
cable tocentralized
controller
Single-phase power supply
220V-50Hz/60Hz
Single-phase power supply
220V-50Hz/60Hz
L N
Y/G
P
Q E
Single-phase powersupply
220V-50Hz/60Hz
Three-phase power supply 380V3N-50Hz/60Hz
Three-core
shieldedcable
L1 L2 L3
N
Indoor unit
Outdoor unit
Y/G
P Q E
L N
Y/G
P Q E
X
Y E
Three-core
shielded cable
to centralized
controller
Summary of Contents for CHV Mini Series
Page 1: ...Commercial AirConditioners Service Manual R410A Series...
Page 3: ...CHV Mini VRF 50 60Hz 2 202105 CHV Mini Series ServiceManual...
Page 13: ...CHV Mini VRF 50 60Hz 12 202105 CHV Mini Series ServiceManual...
Page 109: ...108 202105 CHV Mini Series ServiceManual CHV Mini VRF 50 60Hz 1 ExplodedViews...