background image

Wall-mount type of Air Quality Detector 

Model: GTF300-AQ and GTF300-VOC

 

GASTECH is a professional manufacturer in various gas detectors, carbon monoxide detector, carbon dioxide detector, 
oxygen detector, odor detector, VOC detector, hydrogen sulfide detector and carbon monoxide detector. Welcome tour 
our website 

www.gastech.com.tw 

In the display, press ADJ key, to reset the relay action limit. The last words of last row 
might show UP, press ADJ key will increase the setting limit. Press UPDN key, the word 
will change to DN; press ADJ key will decrease the setting limit.

 

Note: this function is available in relay output model only. 

Press NEXT key to enter next function. 
 
In the display, press ADJ key, to reset the relay release limit. The last words of last row 
might show UP, press ADJ key will increase the setting limit. Press UPDN key, the word 
will change to DN; press ADJ key will decrease the setting limit. 

Note: this function is available in relay output model only. 

Press NEXT key to enter next function. 
 
In the display, press ADJ key, to reset the humidity. The last words of last row might show 
UP, press ADJ key will increase the setting limit. Press UPDN key, the word will change to 
DN; press ADJ key will decrease the setting limit. 
In order to improve the accuracy of GTF300-AQ/VOC, please adjust humidity. The default 
relative humidity of gas detector is 65%RH with adjustable range from 40%RH to 80%RH.

 

Press NEXT key to enter next function. 
 
In the display, press UPDN and ADJ keys at same time, to enter calibration function.

 

Press NEXT key to jump calibration function and enter next function. 

Warning! Except necessary, do not execute calibration. It is necessary to execute calibration 
after power on 7 days. An error operating should loss accuracy. 

 
In the display, user has to finish calibration. 
Press ADJ key, to meet ambience CIAQ

.

 In the fresh air, 1 is a recommended 

value. But in some place, user might use a portable air quality detector to know 
the ambience CIAQ. During the calibration the ambience CIAQ must be below 
CIAQ 70. The last words of last row might show UP, press ADJ key will 
increase the calibrating value. Press UPDN key, the word will change to DN; 
press ADJ key will decrease the calibrating value. 
Press NEXT key to finish calibration and enter next function. 
 

In the display, press UPDN and ADJ keys at same time, to enter calibration function. 
Before the calibration, user needs prepare an ampere meter and makes series into analog 
current loop.

 

Press NEXT key to jump calibration function and enter next function. 

Warning! Except necessary, do not execute calibration. It is necessary to execute calibration 
after power on 24 hr. An error operating should loss accuracy. 
Note: this function is available in analog output model only. 
 

In the display, user has to finish calibration. 
The last words of last row might show UP, press ADJ key will increase the 
current output. Press UPDN key, the word will change to DN; press ADJ key 
will decrease the current output. 
Press NEXT key to finish calibration of 4 mA and enter next function. 
 

Calibration 

CIAQ 1  UP 

CIAQ 

Calibration ? 

<UPDN> + <ADJ> 

Calibration 

4 mA    UP 

Analog Output 

Calibration ? 

<UPDN> + <ADJ> 

Relay A. L. 

CIAQ 40 UP 

Relay R. L. 

CIAQ 20 UP 

R. Humidity 

65 %  UP 

Summary of Contents for GTF300-AQ

Page 1: ...ad the Security Notifications in detail firstly 2 The gas detector might install on wall or steel plate please refer following drawing to make marking then drill the holes Do not use the gas detector as a drilling template to avoid fault 3 Due to the space is very small that is impossible to use wrench Therefore to use female expansion bolts on the wall or tap female screws on the steel plate and ...

Page 2: ...te www gastech com tw 2 4 Analog output A recommend fuse is 0 2 A in the above 5 Relay output A recommend fuse is 0 2 A the diode could be 1N4002 or 1N4004 in the above 6 In order to meet waterproof the wiring material and parts should be met the requirement also 7 The wiring size is not less 0 5 mm 2 or 20 AWG In the case of long distance wiring to apply bigger size or 30 VDC power is better 8 Th...

Page 3: ...t sensor Semiconductor target GTF300 AQ hydrogen ethanol isobutene etc GTF300 VOC toluene xylene alcohol ammonia etc sampling method diffusion measure range 1 200 CIAQ Composite Index of Air Quality Refer GASTECH calibration curves or make them by user Resolution accuracy sampling time 1 CIAQ continuity alarm level high alarm resetable analog output 4 20 mA max load resistance 500 ohm N A relay ou...

Page 4: ...concentration of hydrocarbon compounds and hydrogen in the air the more pollution exists the higher CIAQ will show 2 Settings The following operating procedure describes the settings In the operation press NEXT key or idle 3 minutes the display will back to the CIAQ In the display press NEXT key to enter next function In the display press ADJ key the buzzer and flash lamp will action Press ADJ key...

Page 5: ...enter calibration function Press NEXT key to jump calibration function and enter next function Warning Except necessary do not execute calibration It is necessary to execute calibration after power on 7 days An error operating should loss accuracy In the display user has to finish calibration Press ADJ key to meet ambience CIAQ In the fresh air 1 is a recommended value But in some place user might...

Page 6: ...uzzer high limit the detector not only has audible alarm but also provide clear alphanumeric alarm message for users It is the CIAQ high alarm display Press NEXT key the buzzer will mute and the display will back to the normal display If the CIAQ is still higher than buzzer high limit this message and audible alarm will come again that will disappear until the CIAQ is lower than the buzzer high li...

Page 7: ...e of scent sense good but some persons might not accept the smell Although everybody has various different sense of smell that cannot define Anyway the smell depends on the concentration of hydrocarbon compounds in the air 5 2 Smoke detecting GTF300 AQ VOC is very sensitive of hydrogen which generated from smoking or incomplete combustion Therefore GTF300 AQ VOC is suitable for air conditioner man...

Page 8: ...fusion or high concentration that out of CIAQ range dilute detection is possible put GTF300 AQ VOC in the bottle and takes the sample gases then inject bottle and read the CIAQ Neither diffusion or dilute Silicon compounds gases is not suitable to use GTF300 AQ VOC e g SiH4 5 6 The best partner of canary People knew apply canary to detect unknown gas or toxic gas since long ago Canary will die whi...