F-Guard IR3 HD User Manual
10 Performance
The following tables show test results of detection distances and times for different fire
scenarios. Each table lists results for a different sensitivity setting. For liquid fires the size of fire
refers to the size of the pan, filled with the fuel. For gas fires, the length of the plume is listed
.
F-Guard-IR3-HD-ASX1, F-Guard-IR3-HD-ASX2 (Standard
model)
Extreme Sensitivity
Fuel
Pan Size
Distance ft (m)
Average Response
Time (Seconds)
N-Heptane
1 x 1 ft
262 (80)
9.0
N-Heptane
1 x 1 ft
230 (70)
4.1
N-Heptane
1 x 1 ft
98 (30)
1.5
Gasoline
1 x 1 ft
230 (70)
3.6
Gasoline
2 x 2 ft
328 (100)
5.3
Methane
32” plume
148 (45)
3.3
LPG
32” plume
180 (55)
4.8
Diesel
1 x 1 ft
164 (50)
2.9
JP5
1 x 1 ft
164 (50)
5.8
JP5
2 x 2 ft
295 (90)
9.2
Kerosene
1 x 1 ft
164 (50)
4.1
Methanol
1 x 1 ft
131 (40)
4.1
Ethanol
1 x 1 ft
125 (38)
4.2
Isopropanol
1 x 1 ft
180 (55)
3.5
Polypropylene
1 x 1 ft
115 (35)
10.1
Paper
1 x 1 ft
79 (24)
0.9
Syngas
32-in Plume
98 (30)
3.3
Wood
1 x 1 ft
148 (45)
3.8
High Sensitivity
Fuel
Pan Size
Distance ft (m)
Average Response
Time (Seconds)
N-Heptane
1 x 1 ft
197 (60)
3.2
LPG
32” plume
148 (45)
2.9
JP5
1 x 1 ft
148 (45)
4.9
Methanol
1 x 1 ft
125 (38)
5.5