MDE-5151 Direct Pulse Out Option Installation Instructions for Atlas™ 9852K/9853K Pumps/Dispensers · March 2014

Page 1

Introduction

Purpose

This manual provides instructions for installing the Direct Pulse Out Interface Board 
(M13949A001), which allows the pumps/dispensers to use both RS-485 and pulse out 
interfaces for Atlas

 9852K and 9853K pumps/dispensers. This direct pulse out interface 

board will only work with the Atlas 9852K or 9853K models and will not work with any other 
model. This pulse output provides a DC output to indicate the quantity dispensed. The pulse 
rate can be configured by a jumper setting for the rates of 1, 10, 100, 250, or 500 pulses per 
gallon.

The output is an open collector transistor output capable of sinking up to 100 milliamps DC at 
voltages up to 24 VDC. The DC ground for the circuit comes from the Fuel Management 
System (FMS). Since the transistor switches between ground and high-impedance, the 
installer must provide a voltage reference when the transistor is in the high-impedance state. 
This reference voltage is provided by a pull-up resistor installed at the FMS between the pulser 
input and the reference voltage. The value of this resistor is calculated based on the voltage 
and current requirements of the FMS pulser circuit.

Table of Contents

Topic

Page

Introduction

1

Important Safety Information

3

Before You Begin

5

Installing Direct Pulse Out Interface Board

6

Required Tools

Following tools are required for installing the direct pulse out interface board for the Atlas 
9852K and 9853K pumps/dispensers:

• Phillips

®

 Screwdriver

• Pliers

Related Documents

Document 
Number

Title

GOLD

SM

 Library

MDE-4331

Atlas Fuel Systems Installation Manual

Gasboy

®

 Atlas Pumps/Dispensers

PT-1949

Gasboy Atlas Pump and Dispenser Illustrated Parts 
Manual

• Gasboy Atlas Pumps/Dispensers
• Parts Manual

MDE-5151

Direct Pulse Out Option Installation Instructions 

for Atlas

 9852K/9853K Pumps/Dispensers

March 2014

Summary of Contents for Atlas 9852K

Page 1: ...the transistor switches between ground and high impedance the installer must provide a voltage reference when the transistor is in the high impedance state This reference voltage is provided by a pul...

Page 2: ...Pumps Dispensers March 2014 Introduction Introduction Abbreviations and Acronyms Term Description CPU Central Processing Unit ESD Electrostatic Discharge FMS Fuel Management System GOLD Gilbarco Onli...

Page 3: ...is imperative to your safety and the safety of others to understand the procedures before beginning work Follow the Regulations Applicable information is available in National Fire Protection Associa...

Page 4: ...cy personnel Location of accident for example address front back of building and so on Nature of accident for example possible heart attack run over by car burns and so on Age of victim for example ba...

Page 5: ...rostatic precautions may damage electronic components and void warranty CAUTION To prepare the site and dispenser for the installation proceed as follows 1 Inform the manager 2 Barricade the unit to b...

Page 6: ...emove the front panel 2 Remove the two bolts located over the tabs of the bezel assembly Lift the bezel assembly upward and out to remove 3 Loosen and remove the two screws located on the left and rig...

Page 7: ...e unit with only one pulser it connects to the first four pins of P2 Connect the pump handles cable to P4 Locate the DC cable connector labeled J3 4 conductor cable with brown orange yellow and gray w...

Page 8: ...Company Installing Direct Pulse Out Interface Board 9 Complete the wiring between the FMS and DC Junction Box J box as shown in your FMS Installation Manual For more information refer to MDE 4331 Atla...

Reviews: