GARDTEC GT490X Engineer’S Reference Manual Download Page 1

G

G

G

G

T

T

T

T

4

4

4

4

9

9

9

9

0

0

0

0

X

X

X

X

C

C

C

C

o

o

o

o

n

n

n

n

tt

tt

rr

rr

o

o

o

o

ll

ll

  

  

P

P

P

P

a

a

a

a

n

n

n

n

e

e

e

e

ll

ll

Engineer’s 

Reference Guide

490X 1.qxd  11/07/2006  12:32  Page 1

Summary of Contents for GT490X

Page 1: ...G G T T T T 4 4 4 4 9 9 9 9 0 0 0 0 X X X X C C C C o o o o n n n n t t t t r r r r o o o o l l l l P P P P a a a a n n n n e e e e l l l l Engineer s Reference Guide 490X 1 qxd 11 07 2006 12 32 Page...

Page 2: ...gramming Panic 60 Programming PGM2 PGM3 Timers 62 Programming Reset Modes 66 Programming Sounder Levels 68 Programming PGM 1 Timers 70 Programming Engineer Code 72 Programming Service 73 Programming C...

Page 3: ...a suitable re chargeable lead acid battery permanently connected to the appropriate terminals All documentation and manuals must be thoroughly read by suitably qualified installation personnel prior...

Page 4: ...nel to suit the requirements of the sys tem The 490X control panel uses 32 character LCD Remote Keypads for control of the system via User Code s and programming of the system via an Engineer Code The...

Page 5: ...until all your wiring is in place Wiring Considerations With the exception of the mains wiring all interconnections should be made with multicore 7 02 alarm cable Good wiring practice should be observ...

Page 6: ...s should be via a 3 Amp fused spur with disconnection facility Page 5 490X Engineer s Reference Guide Consumer Unit 3A Unswitched Fused Spur Control Panel Mains Terminal Block Mains Connection Colours...

Page 7: ...N 16 OHM REMOTE KEYPAD S MAY BE WIRED IN STAR OR DAISYCHAIN FORMAT D2 B D1 A 0V 12V D2 B D1 A 0V 12V LINE IN 3 2 5 OTHER SOCKETS ON PREMISES Note Only replace fuses with correct type value GTAG PROXIM...

Page 8: ...on the variant of keypad fitted external G Tag Proximity Reader s may be fitted to each Remote Keypad Note Please refer to the back of this manual if the Control Panel has been supplied with a 4 Wire...

Page 9: ...MIN 16 OHM Strobe Trigger Bell Strobe Hold Off Bell Trigger Bell Hold Off Supply Tamper Return A5 IN B2 IN C3 B2 A5 Terminal 5 on existing BT Master socket Terminal 2 on existing BT Master socket Ter...

Page 10: ...C Devices 6k8 6k8 4k7 4k7 4k7 4k7 4k7 4k7 4k7 4k7 TZ 6k8 Tamper Zone becomes Zone 9 ONLY when 9 EOL is selected 4k7 N C Devices End of Line Zone Wiring Multiple units can only be used with BS Standard...

Page 11: ...k Note For ELF2 wiring format the 12K resistor must be linked to the positive side of the zone terminals 12K 4K7 6K8 AZx Alarm Tamper Fault Mask AZx 12K 4K7 6K8 Alarm Tamper Fault Mask Zone Doubling D...

Page 12: ...Zones will start at 91 When programming Radio Fobs the numbering of the Fobs will start at 81 Resistor Colour Codes Page 11 490X Engineer s Reference Guide RS485 RADIO EXPANDER CONNECTIONS RS485 RED...

Page 13: ...essing 3 7 YES NO during initial power up will revert all system settings back to defaults with the exception of the User Names and Zone Descriptors c Pressing 4 6 YES NO during initial power up will...

Page 14: ...with the old BS4737 Standards DD243 requirements will still apply Selecting 2 EN2 Panel may be programmed to comply with EN50131 1 for Grade 2 Systems DD243 requirements will still apply 5 Select 2 EN...

Page 15: ...Page 17 for Common Options with Menu Numbers Below is given a complete list of headers Shown in Bold Underline and options that appear under each header Program _ _ _ Zones Headers Options Program Zo...

Page 16: ...ess is defaulted to Off and cannot be changed PGM2 PGM3 Timers PGM 2 Mode PGM3 Mode Timer 1 On Time Timer 1 Off Time Reset Modes Mains Fail Delay Alarm Reset Tamper Reset Alarm Restore On Off Abort Ti...

Page 17: ...y Step Guide to programming the 490X Control Panel Only the major options will be covered in the Step by Step sections After completing the sections you should be confident to program the remaining op...

Page 18: ...er Code 40 Line Fault Sounders 41 Line Fault Mode 42 Line Fault Log 44 PGM 1 Output 46 Main Fail Delay 47 Tamper Reset Mode 48 Backlight Mode 50 Zone Response 51 Zone Types 52 Test Zone Attributes 53...

Page 19: ...Yes The display will show 6 Press Yes The display will show 7 Enter the zone number you wish to program e g 1 followed by Yes The display will show for example 8 Press No The display will show 9 Note...

Page 20: ...hen Unset Recorded to Log when SET Fire Will give Fire alarm when activated pulsed sounders with Control Panel Set or Unset Remains active in Engineer Programming Mode ET Exit terminator Used for fina...

Page 21: ...owed and is Double Knock Zone Off Zone is turned Off Use with caution Norm Key Zone is a Keyswitch Zone for a normal type Keyswitch Bias Key Zone is a Keyswitch Zone for a Bias momentary type Keyswitc...

Page 22: ...the desired character is displayed press the Yes key to move on to the next character Continue until the line is complete 1 2 3 ABC DEF GHI 4 5 6 JKL MNO PQR 7 8 9 STU VWX YZ Space No 0 Yes Delete 12...

Page 23: ...as cleared 24 Press No until the required settings you require are displayed then press Yes The display will show Wiring Modes available are 8 2 Wire Two wires are used for the zone and a global tampe...

Page 24: ...he setting you require is displayed then press Yes The display will show If 8 8 EOL wiring option is required 28 With the display showing Press No until 8 8 EOL is displayed The display will show 29 P...

Page 25: ...equire is displayed Then press YES The display will show 31 With the display showing 32 If you are not using Radio Detectors press Yes and jump to Step 33 Otherwise Press No until the display shows Ra...

Page 26: ...f the Zone s fails the Test when the system is Set the display will show Test Fail when the user Un Sets the system After 20 successful Sets and Un Sets the Zone s will be taken out of Test by the sys...

Page 27: ...ed when Part Set 2 is used When Part Set 3 is used Parts 1 2 are combined and Removed Omitted 43 If you do not wish to enter PT 1 Zone press Yes and jump to Step 47 Otherwise Press No The display will...

Page 28: ...press Yes 52 The display will show Two Chime suites are available on the 490X control panel so for example you would have the Front Door on Zone 1 programmed into Ch1 and the Rear Door on say Zone 6 p...

Page 29: ...dd more Zones to Ch1 repeat from Step 53 56 When you have finished adding Zones to Ch1 press Yes 57 The display will show 58 If you do not wish to enter Ch2 Zone press Yes and jump to Step 62 Otherwis...

Page 30: ...l and activate the sounders as programmed Perimeter Zone Zones programmed as perimeter will activate the alarm as normal but will also activate a comms channel programmed as perimeter DKnock Arm Log Z...

Page 31: ...e Descriptor as External PSU At the end of the Program Zones menu we have a menu called Program Events Tags enter this option and select the Zone number you have programmed as Fault Program the Tag as...

Page 32: ...1 Part 2 Part 3 may have its own Setting Mode 1 Enter into Engineer Mode To do this follow Steps 1 to 4 on page 18 With the display showing 2 Press No The display will show 3 Press Yes The display wi...

Page 33: ...is option will require a Door Contact Set By Time E E Once the user has started to Set the system the system will Set on either the Time expiring or the door opening and closing This option may requir...

Page 34: ...y will show 18 Enter the time you require as the Exit Time in seconds followed by Yes The display will show for example 19 Use the No key to scroll through the Setting Modes 20 When the Setting Mode y...

Page 35: ...display will show 28 Press Yes The display will show The Final Set Delay is a period of time in seconds after the expiry of the Exit Time and is intended to allow any PIRs for example that are on the...

Page 36: ...ns available for Setting Sounders are Always Audible Exit Sounder will be audible for Full Set and all Part Sets Silent If Part 1 Exit Sounder will be silent during a Part 1 Set Silent If Part 2 Exit...

Page 37: ...he display will show Auto Part Set allows the system to decide if the Setting should be Full Set or Part 1 Set In order to use this option the Setting Mode for Full Set MUST be Time E E and a Door Con...

Page 38: ...splay will show 42 Press Yes The display will show 43 This concludes the programming for Setting Modes Press 0 zero to return to Or Press 0 zero until the display shows Program Setting for Auto Part A...

Page 39: ...Note Entry Time 1 is defaulted to 30 seconds but maybe changed to a maximum of 45 seconds Note Entry Time 2 is defaulted to 30 seconds and may not be changed 1 Enter into Engineer Mode To do this fol...

Page 40: ...Time 2 after the theoretical expiry of Entry Time 1 has been reached If set to Off the bells will activate only when both Entry Time 1 and 2 have expired 9 Press No to change the setting followed by Y...

Page 41: ...SAB Self Actuating Bell The Bell terminal stands at 12V and the Bell terminal switches negative on activation SCB Self Contained Bell The Bell and Bell stand at 12V and 0v The 0V is removed on activat...

Page 42: ...as been activated Bell Delay used to be a Police requirement but is now not often used in the UK 11 Press No The display will show Number of Arms is the number of times the bell is capable of sounding...

Page 43: ...tinue after the Bell Time has elapsed Timed Will Time out with the Bell Time 17 Press No until your required setting is displayed then press Yes The display will show The Strobe light will normally co...

Page 44: ...ayed then press Yes The display will show 23 Press No The display will show 24 Press Yes The display will show 25 Press No until the required setting is displayed then press Yes The display will show...

Page 45: ...Proximity Reader s may be fitted to each keypad 1 Enter into Engineer Mode To do this follow Steps 1 to 4 on page 18 With the display showing 2 Press No four times The display will show 3 Press Yes Th...

Page 46: ...ing is displayed then press Yes The display will show 12 Press No The display will show 13 Press Yes The display will show 14 Press No The display will show 15 Press Yes The display will show Program...

Page 47: ...program the Number of Keypads you have on the system It should be noted the there are no jumpers in the RKP to ident them this is done from the program option 18 Press Yes The display will show 19 Pr...

Page 48: ...RKP Default is Off but maybe changed to On It is intended for use with the external prox reader E Reader and monitors the antenna of the reader for being disconnected 29 Press No until the setting you...

Page 49: ...Mode No Return This will allow for connection to GardTec Remote for programming functions 1 Enter into Engineer Mode To do this follow Steps 1 to 4 on page 18 With the display showing 2 Press No five...

Page 50: ...tion will be delayed for the number of seconds programmed With Part Alarm programmed to Off there will be no transmission of Alarm Alarm B or Alarm Abort if the system is Part Set 10 Press No twice Th...

Page 51: ...Central Station Other signals you may require for DD243 are Alarm Abort Zone Exclude Alarm B Confirmed Channel settings available are Off Zone 24Hr Gen Tamper Alert Fire Part Set Open Close Panic Ala...

Page 52: ...play will show 21 Press No until the required setting is displayed 22 Press Yes The display will show 23 Press No until the required setting is displayed 24 Press Yes The display will show 25 Press No...

Page 53: ...g is displayed 30 Press Yes The display will show 31 Press No The display will show 32 Press Yes The display will show 33 Press No The display will show 34 Press Yes The display will show for example...

Page 54: ...ogrammed into the panel From Site Only Remote Access will be initialised by the user On Site Off Modem Functions are disabled 35 Press No until the required setting is displayed then press Yes The dis...

Page 55: ...ll show We will be entering two Phone Numbers If your Central Station has only supplied you with one Phone Number please use the same one twice 43 Press No The display will show 44 Enter Phone Number...

Page 56: ...will only monitor the Dial Tone This setting should only be used on a dedicated telephone line Line Volts Then Line Monitor will monitor the Line Voltage This setting should be used when the control...

Page 57: ...nt to Central Station By having 4 as the setting for this option channel 4 will be inverted If you have reports from the Central Station that the Open Close channels are the wrong way around proceed a...

Page 58: ...rence Guide You may continue to program other Advanced options if required For the purpose of this Step by Step section 57 Press 0 zero three times The Display will show Program _ _ _ Digicom 490X 1 q...

Page 59: ...the required setting is displayed then press Yes The display will show 6 Press No The display will show 7 Press Yes The display will show 8 Press No until the display shows the required setting then...

Page 60: ...it may be delayed if required 14 Press No twice The display will show 15 Enter the time you require in seconds followed by Yes The display will show 16 This concludes the programming for Linefault So...

Page 61: ...should be noted that with PA Bells Only no PA signals will be sent to Central Station Available setting for PA are Bells Only Activating a Panic will only sound the Bells Bells Always Activating a Pan...

Page 62: ...Press No until the required setting is displayed then press Yes The display will show Note Duress is defaulted to Off and may not be changed 6 Press Yes The display will show 7 Press 0 zero until the...

Page 63: ...ogrammed will operate seven days per week you are not able to program separate time for weekends etc 1 Enter into Engineer Mode To do this follow Steps 1 to 4 on page 18 With the display showing 2 Pre...

Page 64: ...et Walktest Mains Fail 5 Press No until the required setting is displayed then press Yes The display will show for example With the PGM2 programmed as Bell the output will operate with the Bell when t...

Page 65: ...will show 13 Enter the On Time minutes followed by Yes The display will show 14 Press No The display will show Repeat for Timer 1 Off Time 15 Press Yes The display will Show Program PGM2 3 Timer 1 On...

Page 66: ...r s Reference Guide 16 This concludes the programming for PGM2 3 Timer 17 Press 0 zero to return to Or Press 0 zero until the display shows Program _ _ _ PGM2 3 Timers 01 Jan 00 00 01 490X 1 qxd 11 07...

Page 67: ...press Yes The display will show When Alarm Restore is turned On the Digi channels programmed with Restore On will be restored when the system is unset rather than when the system is Reset 6 Press No...

Page 68: ...Page 67 490X Engineer s Reference Guide 10 This concludes the programming for Reset Modes 11 To return to Press 0 zero twice 01 Jan 00 00 01 490X 1 qxd 11 07 2006 12 32 Page 67...

Page 69: ...w 4 Press Yes The display will show 5 Press No twice The display will show 6 Enter a value 1 to 9 1 Low 9 High followed by Yes The display will show 7 Press No The display will show 8 Press Yes The di...

Page 70: ...ce The display will show 14 Enter a value 1 to 9 1 Low 9 High followed by Yes The display will show 15 This concludes the program Sounder Levels press 0 zero to move back to Then Press 0 twice to move...

Page 71: ...for PGM1 are shown on page 62 4 Press No until the required setting is displayed then press Yes The display will show With the PGM2 programmed as Bell the output will operate with the Bell when this...

Page 72: ...ow 11 Press No The display will show 12 Enter the time required followed by Yes The display will show The t 00 setting only applies to Fol Fol Pul Pul 13 Repeat Steps 5 to 13 until all the Custom Outp...

Page 73: ...ll show Be careful if you lock your code in If the code is forgotten you may have to return the control panel to the factory to have it unlocked this will be a chargeable service 5 Press No until the...

Page 74: ...display will show 4 Press Yes if you require to save to PTM Otherwise 5 Press No The display will 6 Press Yes if you require to load from the PTM Otherwise 7 Press No The display will show 8 Press No...

Page 75: ...the Service Timer is reset 14 Press No until the required setting is displayed then press Yes The display will show With Engineer Mode programmed as Constant the panel will remain in Engineer Mode unt...

Page 76: ...or ten seconds after a Set or Unset 4 Press Yes The display will show The LED Status refers to the LED in the G Tag E or I reader Choose from Off The reader LED will only show for ten seconds after a...

Page 77: ...een times The display will show 3 Press Yes The display will show 4 Press Yes if you wish to view the Event Log The display will show for example This is the last event in the Log Use the No key to mo...

Page 78: ...ll show 11 Enter the time you require in hours followed by Yes The display will show 12 Press Yes The display will show In this example any voltage over 14V or below 13V will create a warning when the...

Page 79: ...display will show 17 Press No until the required setting for Off Charge Volts max Battery is displayed then press Yes The display will show 18 Press No until the required setting for Off Charge Volts...

Page 80: ...ow for example 22 Press Yes The display will show for example 23 Press Yes The display will show The backlight will Dim at this point 24 Press Yes The display will show 25 This concludes the Program D...

Page 81: ...G Tag is used then it is permissible to set this option to On Sounder Mode default Unconfirmed This option controls the system speakers fitted options are confirmed or un confirmed If Sounder Trigger...

Page 82: ...43 Confirmed Start Delay default 000m May be programmed between 0 120 minutes default 0 If programmed to anything other than 0 the panel cannot send confirmed signals until the time programmed has exp...

Page 83: ...ow backdoor etc etc This feature is not mandatory for DD243 Scenarios Relating to DD234 Sounder Bell Considerations Please note careful consideration should be given when programming Confirm Sounder a...

Page 84: ...les all means of conformation 6 4 3 DD243 Event 1 System Set Event 2 Entry Door Unlocked Confirmed Alarms Disabled Event 3 Open Entry Door entry time starts Event 4 Entry Time Expires inc Entry Time 2...

Page 85: ...mitted To achieve the above Confirmed on entry Off Programming Alarm Confirm 1 Enter into Engineer Mode To do this follow Steps 1 to 4 on page 18 With the display showing 2 Press No sixteen times The...

Page 86: ...lay will show 12 Press Yes The display will show The term Sounder relates to the system speaker s 13 Press No until the required setting is displayed then press Yes The display will show 14 Press No T...

Page 87: ...s The display will show 21 Press No The display will show 22 Press Yes The display will show 23 Press No until the required setting is displayed then press Yes The display will show 24 Press No The di...

Page 88: ...layed then press Yes The display will show 30 Press No The display will show 31 Press Yes The display will show 32 Press No twice The display will show 33 Enter the time required followed by Yes The d...

Page 89: ...Keypad is disabled during Entry Time Of in Ent Alm Keypad is disabled during Entry time or if Entry Time goes through into Alarm 39 Press No until the required setting is displayed then press Yes The...

Page 90: ...odem or on site via a GardTec Modem Patch Lead To program the NovActive sounder s please follow the instructions below Wiring of the NovActive should be carried out in conjunction with the instruction...

Page 91: ...No until the required setting is displayed then press Yes The display will show for example 11 Repeat for Alm Tmp until the required settings are displayed Then press Yes The display will show 12 Pre...

Page 92: ...hows Or As required 6 Press Yes The display will show 7 Press No until the setting you require is displayed Then press Yes The display will show 8 Press No The display will show 9 Press No The display...

Page 93: ...ay will show Program Digicom Channels Set Off Alrm Off UnSet Off PA Off Set Off Alrm Off UnSet Off PA Off 24Hr Off E E Off 12Hr Off Bat Off Tamp Off AC Off LF Off Alert Off Fire Off W D Off Duress Off...

Page 94: ...fault is detected may be silenced by User Code On if Unset Linefault Sounders will operate when the system is Unset and a Linefault is detected may be silenced by User Code FLT if Off A fault tone wil...

Page 95: ...ineer Code The display will show 3 Enter a valid User Code The display will show 4 Press No The display will show 5 Press Yes The system will start to Set 6 Enter the Engineer Code again This will Abo...

Page 96: ...up to 7 5m E Reader Wiring RKP Terminals Single E Reader 7 5m to 15m E Reader Wiring RKP Terminals Details on wiring multiple Readers are provided with the Reader ANT SET 0V ANT SET 0V ANT SET 0V E R...

Page 97: ...proceed as follows 1 Enter the Engineer Code The display will show 2 Enter a valid User Code The display will show 3 Press No The display will show 4 Press Yes The system will start to Set 5 Allow th...

Page 98: ...sers Default Codes Code Length User Names 230V a c 10 50Hz 2K not with E O L 400mS 20mm 125mA Anti Surge 20mm 2A Anti Surge 20mm 1A Quick Blow 20mm 250mA Quick Blow 20mm 2A Anti Surge 13 8V dc Regulat...

Page 99: ...A is available for battery charging This defines a theoretical maximum standby battery capacity of 8 0Ah and a maximum of 666mA available for system power If a smaller capacity battery is used then th...

Page 100: ...e output for the Strobe The negative terminal is switched during an alarm period A maximum of 600mA may be drawn from these terminals see power supply rating above Bell Terminals This pair of terminal...

Page 101: ...g Keypad Zones and use resistor EOL GTAG PROXIMITY READER S 4 Wire Contour RKP A1 A2 if used are connected to the first reader antenna If using an second reader remove the link and connect between A3...

Page 102: ...Page 101 490X Engineer s Reference Guide Notes 490X 1 qxd 11 07 2006 12 32 Page 101...

Page 103: ...Page 102 490X Engineer s Reference Guide Notes 490X 1 qxd 11 07 2006 12 32 Page 102...

Page 104: ...riscogroup com e mail sales riscogroup co uk Technical Support 0161 655 5600 Technical Support Fax 0161 655 5610 RISCO Group UK Ltd reserve the right to amend the software and features without prior n...

Reviews: