The progress of the stopping process is shown on the Message Status Bar. The time value shown (for
example, “20 seconds”), is the time remaining on the minimum stop timer. The pressure value shown is the
amount of pressure in the reservoir that must be vented for the system to be depressurized, or blown-down,
to the appropriate value for the machine. For example, if the machine is designed to vent to 25 PSI in the
reservoir and the reservoir currently has 85 PSI during the stopping process, the Message Status Bar would
display 60 PSI. The motor will be stopped when both the time and pressure requirements have been met,
or a maximum time of 120 seconds if the machine does not fully vent.
After stopping, the display will return to the Ready state.
3
.
9.4 Emergency Stop
The
Emergency Stop
button is located on the front door of the control panel close to the display and is
identified by a red button with a yellow background. The
Emergency Stop
cuts power to outputs on the
controller immediately and stops the machine abruptly. This should only be used in case of emergency
where the machine must be stopped immediately.
Regular use of the Emergency Stop will cause damage to the machine. Always use the Stop button
as described above to stop the machine under normal operation.