Fig. 12 Password (Passwort) (user management)
Commissioning and decommissioning
1
Select access level
2
Input password
1
2
6.3.2 Password (Passwort) (user management)
The control unit has 5 access levels. Access to the displayed pieces of data depends on the authorisation.
Values shaded in white may be edited. Values shaded in grey are protected and cannot be changed with the
currently selected authorisation.
Overview on access levels and authorisations:
Access level
Authorisation
Disabled
(Gesperrt)
View data, changes not possible (automatically blocked after 5 minutes)
Main operation
(Hauptbedienung)
(password: 4762)
Change data of „Process (Prozess)“, „Timer (Zeitschaltuhr)“ and „Time (Uhrzeit)“
Commissioning
(Inbetriebnahme)
(Password: 1499)
Like main operation and additionally change data of „PID“
Device
The operator is not authorised, only authorised service personnel or the manufacturer
can change values.
Authorisation like commissioning and additionally „Set-up analog input (Einstellung
Analogeingang)“.
Manufacturer
(Hersteller)
The operator is not authorised, only authorised service personnel or the manufacturer
can change values (full access).
After the access level has been selected, enter the password. If the password is correct, the field will be
shaded in green. A higher access level is also authorised for the lower access level.
The display remains active for 5 minutes. If it is not touched within these 5 minutes or there is not
input via the touchscreen, the display will be blocked. Before using it again, the user has to unlock
the display by entering the access level and the password.
6.3.3 PID (commissioning)
The parameters for a PID control can be set via the „PID“ screen.
For this purpose, the access level „Commissioning (Inbetriebnahme)“ (or higher) will be required.