background image

8

5.0 Instrumentation

The following instrumentation helps in monitoring dryer 

operation and performance. Instruments which are avail-

able as options are so noted.  
Externally Heated Purge Air dryers are rated NEMA 4 and 

include the following:

•  Solid State Controls
•  Chamber Pressure Gauges
•  Purge Flow Pressure Gauge
•  Switch Failure Alarm
•  Purge Save Module (Option A)
•  Energy Management (Option A)
•  Dew Point Transmitter (Option B)

5.1 Controls

The solid-state dryer controls are located in a polycarbon-

ate, NEMA Class 4/4X, IP66 rated electrical enclosure 

mounted to a center panel located between the two desic-

cant towers. Control features include:

•  15 LED’s to indicate operating status and fault condi

-

tions.

•  Two line text display to provide status and diagnostic 

messages.

•  Upon power loss, dryer “fails safe” (inlet valve remains 

in position).  On power recovery, controller resumes 

where power was lost.

5.2  Chamber Pressure Gauges

A gauge mounted on the gauge panel indicates which 

chamber is on-stream and which is regenerating. The 

gauge for the on-stream tower indicates operating pres-

sure; the gauge for the regenerating tower indicates 0 psig.

5.3  Purge Flow Pressure Gauge

A gauge mounted on the gauge panel of the dryer indicates 

purge airflow.

5.4  Valve Switch-Failure Alarm

Pressure sensors located on each chamber trigger an 

alarm when the drying chambers are not in the correct 

pressure state (for example: chamber does not depres-

surize at the completion of its drying cycle).  The chamber 

pressure switch should be closed on the on-stream cham-

ber and open on the regenerating chamber.  If triggered, 

the dryer control system will energize the red alarm LED 

on the control panel and de-energize the common alarm 

relay.  The alarm automatically clears once the alarm 

conditions are corrected.

5.5  Venturi Blower

This precision engineered venturi blower uses ambient 

air to boost the bed regeneration flow-through capacity.  

It is included with the Energy Management System.

5.6  Energy Management System 

The optional Energy Management System (EMS) au-

tomatically adjusts dryer operation to compensate for 

changes in operating conditions.  Air samples are con-

tinuously taken from the on-stream tower and passed 

over a moisture probe which senses both temperature 

and relative humidity.  The moisture content of the air 

within the desiccant bed is then precisely determined.  

The on-stream tower will not depressurize and regener-

ate until a predetermined set point has been reached.  

This elimination of unnecessary regeneration reduces 

energy consumption and extends dryer desiccant and 

component life.

5.7  Dew Point Transmitter

This option monitors and displays outlet pressure dew 

points and provides an alarm signal if the dew point 

exceeds user-specified set point.  Recommended cali

-

bration interval is 12 months.  Contact the service depart-

ment for details.
Operation – The dew point is measured at the dryer oper-

ating pressure and is displayed in the operator interface.  

If the dew point is outside of the temperature range, the 

display will indicate an over-range (high dew point) or 

under-range (low dew point) condition.  A defective sen-

sor assembly or an electronics malfunction could also 

cause the transmitter to indicate under-range.

Summary of Contents for DHP Series

Page 1: ...3 645 4th Edition For Sales and Service 800 883 2477 Or visit Sales and Service at www gardnerdenverproducts com Contents 1 0 General Safety Information 2 2 0 Receiving Storing and Moving 2 3 0 Descri...

Page 2: ...GER WARNING and CAUTION are used to indicate hazard seriousness levels as follows DANGER Immediate hazard which will result in severe injury or death WARNING Hazard or unsafe practice which could resu...

Page 3: ...nt bed desorbs the moisture from the desiccant and carries the desorbed water out of the dryer The heater and venturi suction valve are turned off when the Heat Saver temperature sen sor detects bed h...

Page 4: ...bypass piping may be installed to allow uninter rupted airflow during servicing If the downstream appli cation cannot tolerate unprocessed air for short periods install a second dryer in the bypass l...

Page 5: ...licable from the desiccant fill port at the top of each tower Refer to Figures 3 and 3a for the fill port location CAUTION Pouring desiccant creates a fine dust safety goggles gloves and a dust mask s...

Page 6: ...OVED FOR CLARITY P L S GAS INLET M T GAS OUTLET CONNECTION TOP VIEW R SLOT TYP 4 PLACES CENTERLINE OF CUSTOMER DRY GAS OUTLET CONNECTION H CENTERLINE OF CUSTOMER WET GAS INLET CONNECTION E MAX F G C D...

Page 7: ...1 2 NPT 2 NPT 2 NPT 3 FLANGE 3 FLANGE 3 FLANGE 3 FLANGE 3 FLANGE 3 FLANGE 4 FLANGE 4 FLANGE 4 FLANGE T 1 1 2 NPT 1 1 2 NPT 2 NPT 2 NPT 3 FLANGE 3 FLANGE 3 FLANGE 3 FLANGE 3 FLANGE 3 FLANGE 4 FLANGE 4...

Page 8: ...sed on the on stream cham ber and open on the regenerating chamber If triggered the dryer control system will energize the red alarm LED on the control panel and de energize the common alarm relay The...

Page 9: ...OWER INSULATION OPTIONAL HIGH TENSION ENCLOSURE CONTROL ENCLOSURE RIGHT TOWER PRESSURE GAUGE PURGE PRESSURE GAUGE REAR VIEW TOWER INLET VALVE ASME CODE TAG HOT PIPE INSULATION OPTIONAL HEATER TEMP THE...

Page 10: ...RIGHTTOWER PRESSURE GAUGE HIGHTENSION ENCLOSURE CONTROL ENCLOSURE ASME RELIEFVALVE HOT PIPE INSULATION OPTIONAL PURGE INLET CHECK VALVE IN VXD TOWER INLET VALVE ASME CODE TAG PURGE ADJUSTING VALVE REM...

Page 11: ...the Right Purge Check Valve down through the right tower and exits through the Right Tower Purge Ex haust Valve D The Heater is de energized when the Right Chamber temperature sensor detects desiccan...

Page 12: ...st muffler Next Purge Supply Valve E and Left Tower Purge Exhaust Valve D are opened and the Heater is turned on The Venturi Blower Intake Shutoff Valve F is opened Purge air passes through the ventur...

Page 13: ...FF position to en able both the dryer fault alarms and service alarms to activate the common alarm This is the default configuration Install jumper JP6 in the ON position if the common alarm is to act...

Page 14: ...the Heated Desic cant Dryer Control a Program Mode b Setup Mode c Alarm Service Mode d Display Mode e Test Mode 2 Each Mode is described below 6 5 4 Program Mode 1 Press and hold and for 3 seconds to...

Page 15: ...et Point for Dew Point Demand Control This feature is only active when JP3 is on DPNT CNTL SETPT XX C XXX F 1 Press to increment the setting to the desired value a Standard set point is 30 C 22 F b Th...

Page 16: ...acknowledge the selection and move to next screen Exit Program Mode when there are no more active screens to display 6 5 5 Setup Mode 1 Press and hold for 3 seconds to enter Setup Mode 2 Setup Mode i...

Page 17: ...le sequence is stopped a local alarm is displayed and the common alarm relay is de energized c Alarm Left Tower Regenerating High Pressure will be displayed if regenerating the left tower Alarm Right...

Page 18: ...TWR DEW POINT UNDER RANGE ALARM RIGHT TWR DEW POINT OVER RANGE ALARM LEFT TOWER TEMP UNDER RANGE ALARM LEFT TOWER TEMP OVER RANGE ALARM RIGHT TWR TEMP OVER RANGE ALARM RIGHT TWR TEMP UNDER RANGE ALARM...

Page 19: ...Energy Management Control the dryer sequence continues but bypasses the HOLD step and proceeds to tower switchover after 4 hours of drying iii This alarm is self clearing at which time the alarm LED s...

Page 20: ...d to the controller whether the controller is switched on or off When a service time interval expires see also 14 d below the controller operates as follows a The service LED blinks and the appropriat...

Page 21: ...reminder filters HOURS TO SERVICE FILTERS XXXX Service reminder desiccant HOURS TO SERVICE DESICCANT XXXX Service reminder valves HOURS TO SERVICE VALVES XXXX Outlet Dew Point Displayed only if JP3 i...

Page 22: ...en Open Open then Closed 2PS Closed Closed then Open Open Open Open Open then Closed Closed Closed Closed Closed Closed Closed LT drying solenoid B On On On On On On Off Off Off Off Off Off LT depress...

Page 23: ...essurized Exception If switching failure is disabled then pressure condition is ignored Screen 7 Step 7 TEST7 RT DRYING RT XX C XXX F Screen 8 Step 8 TEST8 DEPR LT LT XX C XXX F NOTE Sequence step wil...

Page 24: ...s dust in the muffler cartridges This sometimes occurs after start up due to dusting of the desiccant during tower filling and dryer transport If the tower pressure gauge of the off stream tower rises...

Page 25: ...valves will react as follows 1 For models with poppet style inlet valves models 300 600 both inlet valves will open Both towers will repressurize 2 For models with butterfly inlet valves models 750 3...

Page 26: ...on of the inlet temperature F xxx ASCII representation of the heater temperature F xxx ASCII representation of the left bed temperature F xxx ASCII representation of the right bed temperature F xxx AS...

Page 27: ...27 Example If jumper 8 5 and 1 are installed a value of 128 16 1 145 is returned To decode the algorithm If number 128 jumper 8 on number number 128 If number 64 jumper on number number 64 etc...

Page 28: ...desiccant Layer 1 must be installed first at the bottom of the vessel followed by layer number 2 etc until the complete charge of desiccant has been installed e Utilizing an appropriate sized funnel f...

Page 29: ...placement may be required sooner if pressure drop across the cartridge prevents the Dew Point Analyzer from operating properly WARNING The Dew Point Analyzer filter housing is a pressure containing de...

Page 30: ...failed to close 6 Drying tower Depressurization Valve failed to close 7 Regenerating tower Outlet Check Valve failed to close 1 Check compressor supplying dryer 2 Check equipment downstream of dryer...

Page 31: ...rge Exhaust Valve failed to close 3 Regenerating tower Depressurization Valve failed to close 1 Check pressure switch operation using tower pressure gauge for comparison Replace switch if defective 2a...

Page 32: ...Left Tower or Right Tower 1 Desiccant bed overloaded 2 Poor regeneration 3 Moisture probe damaged or defective 4 Loss of desiccant drying capacity 1 Check inlet air flow rate temperature and pressure...

Page 33: ...PRESSURE PSIG PURGE SET PRESSURE PSIG MODEL ORIFICE DIA IN 300 7 32 34 58 400 1 4 34 37 500 9 32 34 47 600 5 16 34 38 750 11 32 34 46 900 3 8 34 58 1050 13 32 34 25 1300 29 64 34 38 1500 31 64 34 50...

Page 34: ...PHIC SYMBOLS FOR FLUID POWER DIAGRAMS SOLENOID VALVES A C E F ARE SHOWN DE ENERGIZED AS SHOWN FLOW DIRECTION IS INDICATES OPTION 3 2 1 PILOT GAS LINE RIGHT CHAMBER REGEN LEFT CHAMBER DRYING NOTES 4 SO...

Page 35: ...INLET VALVE V1 LEFT V2 RIGHT 2 PURGE EXHAUST VALVE V3 LEFT V4 RIGHT 3 PURGE CHECK VALVE V5 LEFT V6 RIGHT 4 OUTLET CHECK VALVE V7 LEFT V8 RIGHT 6 PURGE HEATER WITH INSULATION 7 HEATER TEMPERATURE THER...

Page 36: ...S SOLENOID VALVES A C E F ARE SHOWN DE ENERGIZED AS SHOWN FLOW DIRECTION IS INDICATES OPTION 3 2 1 PILOT GAS LINE RIGHT CHAMBER REGEN LEFT CHAMBER DRYING NOTES 4 SOL H RTD4 HS1 SOL D RTD 1 V3 V4 SOL C...

Page 37: ...E P R E S S U R IZ A T IO N R E P R E S S U R IZ A T IO N S W E E P 55 3 H O L D 2 176 55 S W E E P 3 L O S S O F P O W E R H O L D FIXED CYCLE TIMING LEFT CHAMBER DRYING RIGHT CHAMBER REGEN RIGHT CH...

Page 38: ...ONLY 3 G 1 26 RED GREEN BROWN BLACK EXTERNALLY LOCATED OPTION 102 101 120VAC 101 110 RED BLACK GREEN 21 ADD FOR MODELS 900 3200 ONLY TB5 90 91 ORANGE 32 33 34 35 90 91 EXTERNALLY LOCATED DEWPOINT TRAN...

Page 39: ...1 26 RED GREEN BROWN BLACK EXTERNALLY LOCATED OPTION 102 101 120VAC 101 110 RED BLACK GREEN 21 ADD FOR MODELS 900 3200 ONLY TB5 90 91 ORANGE 32 33 34 35 90 91 EXTERNALLY LOCATED DEWPOINT TRANSMITTER 4...

Page 40: ...URE CONTROL ENCLOSURE 22 46 6 4 11 15 17 14 2 27 58 11 23 AIR OUT LEFT CHAMBER RIGHT CHAMBER AIR IN 1 9 45 44 3 10 42 43 FRONT VIEW SIDE VIEW RIGHT CHAMBER REMOVED FOR CLARITY REAR VIEW 7 8 Gardner De...

Page 41: ...4237 G3154237 G3154237 G3154237 1 17 Exhaust Muffler G3204478 G3130773 G3130773 G3072056 2 Exhaust Muffler Replacement Core G3126761 G3121200 G3121200 G3094580 1 2 22 Purge Adjusting Valve G1196180 G1...

Page 42: ...LOSURE 45 46 25 23 11 5 27 2 54 15 14 11 4 10 44 7 8 22 3 42 9 1 1A 17A 6 MODEL 750 17 2 43 FRONT VIEW SIDE VIEW RIGHT CHAMBER REMOVED FOR CLARITY REAR VIEW AIR IN AIR OUT LEFT CHAMBER RIGHT CHAMBER I...

Page 43: ...G3072056 N A N A N A N A N A 2 Exhaust Muffler Replacement Core G3094580 N A N A N A N A N A 2 2 17a Depress Muffler N A G3071392 G3071392 G3071392 G3090655 G3090655 2 Depress Muffler Replacement Cor...

Page 44: ...CONTROL ENCLOSURE 8 7 25 22 46 6 10 4 11 15 54 2 14 5 27 11 23 1 1A 3 9 42 45 44 17A 43 FRONT VIEW SIDE VIEW RIGHT CHAMBER REMOVED FOR CLARITY REAR VIEW AIR OUT LEFT CHAMBER RIGHT CHAMBER AIR IN Gard...

Page 45: ...Air Filter Element G3158592 G3158592 G3158592 1 15 Pilot Air Pressure Regulator G3154237 G3154237 G3154237 1 17a Depress Muffler G3130773 G3130773 G3130773 2 Depress Muffler Replacement Core G3121200...

Page 46: ......

Page 47: ......

Page 48: ...uiring routine replacement are not warranted Unauthorized service voids the warranty and any resulting charge or subsequent claim will not be paid THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF AL...

Reviews: