MMC Profibus
Option Module
138
MMC Hardware Manual
G & L Motion Control Inc.
8.3
LEDs
The two configuration port LEDs and the two Profibus port LEDs are
described below.
Table 8-3: Description of Profibus Port LEDs
Profibus Port
LED
Color
State
Definition
Network status
Green
OFF
Off-line
ON
On-line, no physical layer or
data layer errors (or Profibus
cable not connected)
Red
ON
On-line, bus error (baud rate or
wiring problem)
Scanner status
Green
OFF
No power or else reset
asserted, interface closed
ON
Scanner communicating, data
exchanging, no slave device
errors
Flashing
Scanner in start-up
Red
ON
At least one slave faulted
Orange
ON
Configuration (download)
mode
Configuration
Port
IN
Red
Flickering
Data is being passed to the
module
OFF
No data to the module
OUT
Red
Flickering
Data is being passed from the
module
OFF
No data from the module
Summary of Contents for MMC-A2
Page 1: ...Standalone MMC TM Hardware Manual Version 15 0 G L Motion Control Inc...
Page 2: ......
Page 36: ...Installation Operation Maintenance 28 MMC Hardware Manual G L Motion Control Inc...
Page 124: ...Standalone Digital MMC Control 116 MMC Hardware Manual G L Motion Control Inc...
Page 136: ...MMC Ethernet TCP IP Option Module 128 MMC Hardware Manual G L Motion Control Inc...
Page 175: ...CE and EMC Guidelines G L Motion Control Inc MMC Hardware Manual 167...
Page 176: ...CE and EMC Guidelines 168 MMC Hardware Manual G L Motion Control Inc...
Page 177: ...CE and EMC Guidelines G L Motion Control Inc MMC Hardware Manual 169...
Page 178: ...CE and EMC Guidelines 170 MMC Hardware Manual G L Motion Control Inc...
Page 186: ...Appendix A Operation Details 178 MMC Hardware Manual G L Motion Control Inc...