GWF-7075 Manual —
LS10147-002GF-E:G 10/5/2022
79
Function Keys
System Operation
7.8.4 Using a Recorded F-Key Macro
1.
From the Idle screen on any annunciator in the site, press the F-Key you want to activate.
2.
Once finished, deactivate the macro by pressing the F-Key again.
7.8.5 F-Key Status Event
When an F-Key is enabled, it activates its corresponding F-Key Active Event. This is a status type event that can activate outputs without
showing any status on the annunciator displays. This option should be used for ancillary purposes only.
7.8.6 F-Key Map Inhibit
The F-Keys have the ability to temporarily disable event/output group mapping. This option can be setup to allow for testing purposes where
the notification of an entire building is not desired during a test. This option is programmable for each output group Map through the HFSS
Honeywell Fire Software Suite.
When an F-Key is active and a map in the system is set to be disabled by Map Inhibit, the system will show a trouble event.