72
GWF-7075 Manual —
LS10147-002GF-E:G 10/5/2022
System Operation
Basic Operation
You can print detector status from HFSS after uploading the information to the software suite.
7.3.12 View Status of a Point
1.
From the main menu, select 2 for Point Status.
2.
From the list that displays, press ENTER to select the module where this point is located. Next, enter the point to display. The screen
that displays will show you if the point has a trouble and will provide sensitivity compliance information. (See Section 7.3.11 above for
complete information about detector sensitivity compliance).
7.3.13 View Alarms, Supervisories, or Troubles
When the system is in alarm, supervisory or trouble, you can press down to view the location of the device.
7.3.14 View System Information
From the Main Menu, press 8 to access the System Information menu.
About Panel
Press 1 to access About Panel to view the panel model, serial number, system version number, and date.
Send/Receive Firmware Updates
The GWF-7075 has the ability to be updated in the field. The most recent GWF-7075 Firmware Update Utility can be downloaded from the
Gamewell-FCI website, www.gamewell-fci.com. Once a panel has been updated using the Firmware Update Utility, you can use
Send/Receive Firmware Updates to forward the firmware to the other panels in the network.
1.
From the System Information menu, press 2 to send a firmware update or press 3 to receive a firmware update. Available panels are
listed in the menu. This feature requires a multi-site installer access code.
2.
Use the up or down arrow key to select a panel to send/receive an update. Press ENTER to start the update process.
SMOKE PHOTO 2.5%
MODULE_33 POINT_4
[Z001] [M33:004] A058
NORMAL >=MORE
Example of detector in compliance
Example of detector not in compliance
ATL=151 (2.5% OB/FT)
ACA=057 M=093 T=109
Clear Air = 058 (01%)
Peak-061 (04%) >=HLP
SMOKE PHOTO ---%
MODULE_33 POINT_4
[Z001] [M33:004] A058
CAL TRBLE >=MORE
ATL=151 (2.5% OB/FT)
ACA=057 M=093 T=109
Clear Air = 058 (01%)
Peak-061 (04%) >=HLP
ATL=Alarm Threshold
ACA=Average Clr Air
M=Maint Threshold
T=Trouble Threshold
CO SMOKE 2.0%
MODULE_33 SENSOR_4
[Z001] [M33:004] AXXX
Sensitivity = 2.0%
CO= xxx ppm
detector ID
detector state
percent obscurity
per foot
Possible states:
• NORMAL: detector sensitivity in compliance with UL and not in alarm
• ALARM: detector in alarm
• CAL MAINT: detector needs maintenance, but not yet in trouble
• CAL TRBLE: detector not in compliance with NFPA72
(Other trouble states could override this message.)
Example of CO detector in compliance
detector ID
percent obscurity
per foot
blanks indicate
detector not in
compliance
detector state
current value
Figure 7.3 Checking Detector Sensitivity Compliance