38
GWF-7075 Manual —
LS10147-002GF-E:G 10/5/2022
Control Panel Installation
Remote Station Applications
2.
Program the NAC circuit as a non silence NAC circuit (see Section 6.5.2).
4.15.5 Transmitter Activated by Dry Contacts
This section describes the connection of a UL 864 listed remote station transmitter to the GWF-7075 FACP dry contacts. The FACP contacts
must be supervised by the remote station transmitter module using end-of-line resistors (ELRs) with a value determined by the transmitter
manufacturer. Power is also provided by the remote station transmitter manufacturer. Refer to the remote station transmitter manufacturer’s
manual for details.
NOTE:
If you need to transmit supervisory or trouble conditions, additional relay modules must be added. Use relay 1 to transmit supervisory
conditions. Use the trouble relay to transmit trouble conditions..
NO
NC
C
TROUBLE
RELAY 2
C
NO
NC
RELAY 1
C
NO
NC
SLC IN
+
_
SLC OUT
SLC PROG
+
_
+
_
SBUS
A
B
+
_
NAC 1
NAC 2
The Trouble relay is a fail-safe
relay. With power applied to the
FACP and no troubles in the
panel, the contacts should be in
the condition indicated.
supervisor
y
alarm
trou
ble
Do not loop wires under terminals.
Break wire runs to provide proper
supervision of connections.
typical input
zone triggers
transmitter
activated by
dry contacts
Figure 4.31 Transmitter Activated by Dry Contacts