Section 2: Installation
2.1 General
Components are ordered and shipped in separate packaging for the enclosure and Basic System
Module kit. The 7100 is intended for installation indoors, in a dry location. The shipping carton
contains an installation drawing, backbox, Basic System Module (BSM), power transformer and
door.
1.
Refer to the System Assembly Drawing, P/N 9000-0457.
2.
The BSM module consists of a main operating board with pluggable terminal strips, an 80-
character LCD display and programming keypad. Install this module immediately unless any
optional modules are to be used in the system. The optional modules are supplied separately,
and should be installed on the BSM before it is mounted in the backbox. Before installing the
BSM into the system backbox, refer to the installation instructions shipped with each module
for the proper installation procedures.
3.
Install the transformer into the backbox.
4.
Connect the transformer to the BSM.
5.
After the BSM is in place, install the door
NOTE:
Installations are to be indoors only, in dry locations, protected from rain, water, and rapid
changes in temperature that could cause condensation. Equipment must be securely mounted on
rigid, permanent walls.
NOTE:
The door can only be installed (or removed) when it is opened at least 90° from the
backbox.