MegaV2 250 Installation Guide, Release 2.2
36
Figure 34: Turning on a module
9
.
To verify that the new module is operating normally, navigate to the module status screen
("Main screen > Status > Modules"), press on the icon of the module that was just
switched on, and verify that the status is "ON" for these five items: PFC, Inverter, Dc relay,
Input relay, Output relay. Verify that the other fields are also normal.
Figure 35: Verifying status of added module
10.
On the same screen ("Status > Modules"), press the Output button, select the replacement
module and verify that the output frequency matches the system nominal value, and that
the output voltage of each phase is within 2 % of the system nominal value.