background image

 

Version 1, 15 June 2020, 5 of 16 

6.0  

INSTALLATION

 

IMPORTANT:  Galvin Specialised products must be installed in accordance with these installation instructions 
and in accordance with AS/NZS 3500, the PCA and your local regulatory requirements. Water and/or electrical 
supply conditions must also comply to the applicable national and/or state standards.  Failing to comply with 
these provisions shall void the product warranty and may affect the performance of the product.

 

 

       

 

BACK MOUNT              SIDE MOUNT

  

1. Remove cabinet door 

1.  Open the cabinet door 
2.  Push hinge up  to allow removal of the door. 
3.  Remove the

 

door from cabinet. 

 

2. Secure the cabinet  

 

Insert cabinet into wall opening. 

 

Mount cabinet in wall using four fasteners, only securing 
hand tight. 

 

If side mounting, make sure door frame has clearance 
and can slide after fastening the cabinet.

 

Note: The cabinet must be mounted with four fasteners for 
stability and strength. This is critical, failure to do this may 
void the warranty. 

 

  

 

3.

 

Connect water lines 

  Before connecting to water lines, all lines must 

be flushed 

  Remove protective vinyl cap from copper tubes. 

  Join each copper tube to the correct main water 

line, taking note of flow direction arrows. Use 
suitable copper joining methods, ensuring no 
flash sits inside the pipeline, this will cause 
damage to the valves.

 

Note: The Galvin Engineering CliniMix 
Thermostatic Mixing Valve must be installed by a 
licensed plumber. If the valve is not installed 
correctly then it will not function correctly and 
may put the user in danger. It may also void the 
warranty of the valve. 

4. Testing and operation 

  Adjust the door door frame until sits flush with wall. 

Completely tighten mounting fasteners and apply sealant 
if necessary. 

  Turn on hot and cold water supply. 

  Check for any leaks 

  Carry out commissioning procedure (see Section 7.0) 

  Check temperature of water is correct. If not, see water 

temperature adjustment settings (see Section 7.0). 

  Fit hinged door back into cabinet and lock with supplied 

key. Ensure instructions are placed in the cabinet for 
future service and maintenance record.

 

 

 

 

 

 

 

       

         

     

     

      

       

Summary of Contents for 101.10.70.10

Page 1: ...ng tempered water to the desired outlets This stainless steel hinged cabinet kit is a lockable cabinet with 20mm copper fittings 2 in and 1 out which allows secure installation and safe simple mainten...

Page 2: ...es 3 0 DESCRIPTION This manual covers the CliniMix Lead SafeTM TMV SS Cabinet Assembly with Universal Door 20 Bottom In Out These are designed to provide tempered water to the desired outlets This mix...

Page 3: ...APH The Galvin Engineering CliniMix Thermostatic Mixing Valve is suitable for many applications The Head loss Characteristic for Mixed Outlet Flow rate versus Balanced Inlet Pressure is shown below in...

Page 4: ...ction within specification on unequal pressures up to 6 1 The mixer has integral isolating valves which permit servicing of the strainer check valve flow regulator and thermostatic cartridge They are...

Page 5: ...ure to do this may void the warranty 3 Connect water lines Before connecting to water lines all lines must be flushed Remove protective vinyl cap from copper tubes Join each copper tube to the correct...

Page 6: ...rtest length of pipe work between the mixing valve and outlet fixture Allow the mixed outlet to flow for at least 60 seconds to allow the temperature to stabilise before taking a temperature reading a...

Page 7: ...Restore the cold water to the TMV After the mixed water temperature has stabilized note the outlet temperature ensuring the outlet temperature has reestablished Now repeat the above test except this t...

Page 8: ...st plugs in the top of the inlet fittings are tight and that there is no evidence of water leakage The TMV must then be recommissioned as per Section 7 0 including temperature adjustment and the shutd...

Page 9: ...rass top assembly screw out the plastic spindle and replace the smaller O ring 5 Carefully remove the spindle from the center of the body 6 Remove O ring from spindle Replace with O ring supplied in t...

Page 10: ...OR WM TMV1 1 2 WM ISO 1 INLET ISOLATOR ELBOWS PAIR FOR WM TMV1 1 3 WM NRV 1 INLET NON RETURN VALVE FOR WM TMV1 PAIR 1 4 WM STR 1 INLET STRAINERS FOR WM TMV1 PAIR 1 5 WM TPKIT 1 THERMOSTAT PISTON SHUTT...

Page 11: ...r s recommendation the ode and all relevant statutory and local tate or erritory requirements 4 The TMV must be returned to Galvin Engineering together with a fully and correctly completed Galvin Engi...

Page 12: ...ntrol valves to ensure inlet conditions are within range Clean strainers ensuring debris is removed Either full hot or cold flowing from the outlet fixture Valve is incorrectly set Hot Cold water has...

Page 13: ...___________________ Model No ________________________ Size _________ Valve Location Building _____________________________________________________________________ Valve Identification No _____________...

Page 14: ...k It is hereby certified that all the commissioning work has been carried out by the undersigned in accordance with the requirements of the Codes of Practice indicated prior Date of Valve Commissioned...

Page 15: ...Outlets in Use One Outlet in Use All Req d Outlets in Use 1 2 3 4 5 6 7 8 9 10 11 Give details of brand and model designation Commensurate with the design flow rate for the mixing valve Note An accura...

Page 16: ...e ______________________ Date _______________________ Maintenance Tests Yes Date of Previous Service ______________________________________________________________________ Previous Service carried out...

Reviews: