Figure 5-39: Expanded Modbus Nodes
There are several columns in the Modbus list table. The first is
Modbus Items
which shows
the Modbus list tree and the various data points that are in each node (Figure 5-38).
Register
is the most important, as it shows the address of each data point. These addresses are
essential for setting up the device that will read the Modbus list, so it knows which data point
is output to which register.
Type
shows the type of each data point. Possible values in this
column include Boolean, unsigned long, and float. Most data points are either Boolean or
Float. Floats can be output in the short and long nodes, but the decimal points will be lost.
Certain data points have specific units associated with them, and these will be shown in the
Units
column. If a data point does not have units associated with it, this column will show a
value of
Unknown
for that data point. In the
Value
column, Boolean data points will have
either a value of
True
(if on) or
False
(if off). Numerical data points will show the value
currently entered in the given data point. The
Permissions
column shows whether a given
data point is
Read Only
or
Writeable
. Writeable data points are the only data points that can
be written to remotely through Modbus.
Summary of Contents for ProTech903
Page 2: ......
Page 96: ...Revision 14 96 August 02 2019 Figure 5 19 Event Log...
Page 122: ...Revision 14 122 August 02 2019 Figure 5 38 Typical Modicon with Floating Point List...
Page 124: ...Revision 14 124 August 02 2019 Figure 5 40 Expanded Modbus Nodes...
Page 175: ...Revision 14 175 August 02 2019 Figure 9 17 Non Isolated 4 20 mA Inputs...
Page 190: ...Revision 14 190 August 02 2019...