635-SERIES HARDWARE M ANUAL
Chapter-Page
2-30
635-DSI Examples of How DSI Sections Function Independently
This table clarifies how the sections can work independently. You don’t have to put the same hardware on one
section as you do on the other section.
However, you do have to stay under the 64-device max CPU count.
Table 20: Examples of DSI Sections Functioning Independently
Functions
635-DSI SECTION-1
635-DSI SECTION-2
DSI EXAMPLE 1
635-DRM Remote Doors
635-DRM Remote Doors
Both sections = same use
DSI EXAMPLE 2
635-DRM Remote Doors
clocks
Each section = different use
Note: only in the case of Remote DRMs, the reader technology and card format can be mixed
Wireless Function
635-DSI SECTION-1
635-DSI SECTION-2
DSI EXAMPLE 1
Schlage AD400 – Wgn dedicated
Schlage AD300 – Wgn dedicated
Dedicated card format
DSI EXAMPLE 2
Schlage AD400 & AD300 (MIXED) Schlage AD300 – dedicated
Section-1 mixed AD300/400
DSI EXAMPLE 3
Assa Aperio
Salto Salis
Each section = different use
NOTICE: AD300 & AD400 are the only readers that can mix on the same section (provided they are all the same Card Format
(i.e. ABA vs Wiegand)). You cannot mix ABA and Wiegand on the same section with any wireless readers.
Inputs/Outputs
635-DSI SECTION-1
635-DSI SECTION-2
DSI EXAMPLE 1
635 INPUT MODULES
635 INPUT MODULES
Both sections = same use
DSI EXAMPLE 2
635 INPUT MODULES
600 OUTPUT MODULES
Each section = different use
DSI EXAMPLE 3
600 OUTPUT MODULES
600 OUTPUT MODULES
Both sections = same use
Table 21:
Mapping the DSI “Section Use” in the SG Software
Section Use
is set in the System Galaxy in the DSI Programming screen before you Walk-Test the system. Most
are self-explanatory. You must configure each DSI Section with the appropriate setting.
Purpose
Boards Needed
“SECTION USE” in System Galaxy
Not in use
n/a
UNUSED
Aperio Wireless Readers
635 DSI
ASSA ABLOY Aperio
Salto Salis Wireless Readers
635 DSI
Salto Salis RF
Schlage (ABA) AD300 hardwired
635 DSI
PIM ABA Readers
Schlage(ABA) AD400 Wireless
Schlage (Wgn) AD300 hardwired
635 DSI
PIM Wiegand Readers
Schlage (Wgn) AD400 Wireless
Veridt CAC Readers
635 DSI
Veridt CAC Readers
Remote Door /Readers
635 DSI & 635-DRM (Dual Reader Mod)
RS-485 Door Modules
Inputs
635 DSI & 635- Input Modules
RS-485 Input Modules
Outputs (general purpose)
635 DSI & 600- Output Relay Boards
Output Relay
Elevator Control
635 DSI & 600- Output Relay Boards
Elevator Control Relay
Cypress Clock
635 DSI
LCD Display
635 DSI
LCD 4x20 Display
GO TO Step 10- Wiring Field Devices
to find wiring diagrams for the 635 DSI.