GAI-Tronics 013-02-0096-001 Installation Instructions Manual Download Page 9

Pub. 42004-556A 

IP Controller 

Page 8 of 8

 

P:\Standard IOMs - Current Release\42004 Instr. Manuals\42004-556A.docx 

01/21 

Connection ......................................................................................................................... RJ-45 T568B jack 

Maximum cable length ......................................................................................................................... 100 m 

Audio 

Output 

Audio level ........................................................................................................ 0.775 V 

RMS

 at 1 kHz (600 Ω) 

Frequency response ................................................................... 300–3,400 Hz, +0/−3 dB reference to 1 kHz 

Distortion ...................................................................................... <1% THD @ 1 kHz to 1 V 

RMS

 into 600 Ω 

Isolation ........................................................................................................................................... 500 V 

RMS

 

Control Output .................................................................................................. Isolated Normally Open SSR 

Maximum voltage .................................................................................................................. 50 V dc 

Maximum current.................................................................................................................. 100 mA 

Input 

Input level ..................................................................................................................................... 0.775 V 

RMS

 

Input impedance ................................................................................................................... >50 kΩ at 1 kHz 

Bandwidth ................................................................................. 300–3,400 Hz, +0/−3 dB reference to 1 kHz 

Isolation ........................................................................................................................................... 500 V 

RMS

 

Control Input ......................................................................................................................... N.O. dry contact 

Open circuit voltage ............................................................................................... 3.3 V dc (typical) 

Short circuit current  ............................................................................................ 35 µA (maximum) 

Status LEDs ................................................................................................. Power, PA in use, System status 

I/O Control 

Inputs 

Open circuit voltage ............................................................................................................ 3.3 V dc (typical) 

Short circuit current .......................................................................................................... 35 µA (maximum) 

Outputs 

Maximum voltage ............................................................................................................................... 30 V dc 

Maximum sink current per output ...................................................................................................... 100 mA 

Mechanical 

Unit dimensions .................................................... 43.7 H × 215.9 W × 197.9 D mm (1.72 × 8.50 × 8.91 in) 

Unit weight............................................................................................................................... 2.4 kg (5.2 lb) 

Environmental 

Operating temperature range ............................................................................................... −20 °C to +55 °C 

Relative humidity ..................................................................................................................................... 95% 

Approvals

 

CE Mark 

NRTL ..................................................................................................................................... UL/CSA 60065 

Summary of Contents for 013-02-0096-001

Page 1: ...ty Notice 1 General Information 1 Important Safety Instructions 2 Front Panel Indicators Control 3 Rear Panel Connections 3 Internal 3 Installation 3 Safety Guidelines 3 Location 4 Desktop 4 Rackmount...

Page 2: ...ly to any third party General Information The Model 013 02 0096 001 IP Controller is the principal component of an IP PAGA public address and general alarm system This standalone IP controller is suit...

Page 3: ...inputs and outputs are available via IP MIMs monitored input modules or IP MRMs monitored output modules Connect IP access panels for speech broadcasts and manual alarm emergency message activation Ad...

Page 4: ...3 IP controller Rear View Internal The IP controller contains one primary internal component see Figure 4 E3 IP Controller PCBA Central processing unit digital communication speech recording and play...

Page 5: ...eet and set the unit on a stable level surface Rackmount Use GTC Kit No 12625 001 to mount the IP controller in an standard EIA 19 inch rack see Figure 5 The controller is 1 75 inches tall 1 U of rack...

Page 6: ...es link status yellow LED indicates activity 2 Terminate the connector in accordance with the T 568B wiring method Earth The E3 IP controller requires bonding to earth ground 1 Install a ring lug on a...

Page 7: ...ion and maintenance of the installed Elemec3 IP access panels Inputs Outputs The IP controller has eight unsupervised inputs and eight outputs to initiate events in the system see Figure 3 Connect eac...

Page 8: ...ec3 Portal application for detailed status information Blinking Red Fault acknowledged Amber Non critical fault PWR Blue Power is on Off No power The IP controller displays system status via the E3 Po...

Page 9: ...nput level 0 775 V RMS Input impedance 50 k at 1 kHz Bandwidth 300 3 400 Hz 0 3 dB reference to 1 kHz Isolation 500 V RMS Control Input N O dry contact Open circuit voltage 3 3 V dc typical Short circ...

Page 10: ...of the Contractor s personnel from the work site Re performance of services shall be Buyer s sole and exclusive remedy and in no event shall GAI Tronics warranty obligations with respect to services e...

Reviews: