17
5-4.4 Oil Connection
Free Standing External Boilers are supplied with a pump set for single pipe oil system.
The oil pipe and electric cable should also enter through the cut-outs provided in the
bottom panel - see fig 5-4c.
INST
INST
INST
INST
INSTALLA
ALLA
ALLA
ALLA
ALLATION 5
TION 5
TION 5
TION 5
TION 5
FIRE VALVE SENSOR
FIXED ABOVE BURNER
OIL HOSE
✓
FLOW
FIRE VALVE
SHUT OFF VALVE
FILTER
✓
✓
SUPPLIED WITH BOILER, SEE SECTION 13.
✓
✓
Fig. 5-4c Recommended Two Pipe Oil Connection
1
2
4
3
1. OIL SUPPLY
2. ELECTRICAL SUPPLY
3. FLOW AND RETURN PIPES
FULLY INSULATED
4. RAWL BOLTS FOR BOILER FIXING
Fig. 5-4b Base Details
Fig. 5-4d External Boiler Flue Assembly
SEAL
FITTED INSIDE TERMINAL
SCREWS X 4
MAIN CASE
FLUE BEND
FLUE TERMINAL
GASKET
FIT FLUE GUARD IF
APPLICABLE.
5-4.5 Fitting the Flue
1. Fit flue bend with gasket to Boiler.
2. Fit seal inside flue terminal.
3. Lubricate seal with lubricant supplied and fit terminal with 4 screws.
4. Fit terminal guard.