6.1 Technical data

Weight: 28 kg

Dimensions: 898 x 520 mm

Electrical connection

Pay attention to the rating plate data.

The mains connecting cable must at least
correspond to the type H 05 VV-F G 0,75.

When replacing the mains cable, you must
dismantle the tubular connection piece (undo 
2 screws).

The appliance must only be connected by an

authorised specialist.

The specialist is respon-

sible for perfect functioning of the appliance at its
installation location. He must explain the operating
principle of the appliance to the user with refe-
rence to the operating instructions. He must explain
to the user how the appliance can be isolated from
the mains whenever required.

Connection possibilities

The extractor hood was conceived for the exhaust
air or air recirculation mode. The exhaust air can be
routed into a separate exhaust air shaft or directly
into the open through the outside wall.

The connector of the connecting cable is connec-
ted to the socket that is located behind the duct
cover on the wall. If this is not possible, it must be
possible to isolate all poles of the appliance from
the mains by way of the domestic fuse, or by means
of accessible isolating device with a contact gap 
of at least 3 mm.

6.2 Installation

The applicable regulations of the energy supply
companies and the 

regional construction

regulations

must be observed when installing 

the hood.

The minimum distance from the worktop to the
bottom edge of the wall hood is for electrical
appliances 600 mm and for gas appliances 670 mm.

The wall hood was conceived for the 

exhaust air

or air recirculation mode

. The exhaust air can be

routed into a separate exhaust air shaft or directly
into the open through the outside wall.

It is not allowed to pass the exhaust air into a flue 
or exhaust air chimney that is in operation or into a
shaft that is linked to the heating basement. Consult
the chimney sweep responsible for your district
whenever you wish to pass the exhaust air into a
chimney that is not in operation.

During the course of planning

, a chimney sweep

must be consulted if a room air-dependent hearth 
is operated in the same room as the one in which a
hood is operated in the exhaust air mode. Adequate
incoming air must be ensured. The applicable
construction and safety regulations must be
observed.

Adequate incoming air must be ensured if a wood,
coal, gas or oil heater or an open hearth is operated
in the same room as the one in which the hood is
installed.

Safe operation is possible whenever the partial
vacuum in the place where the firing equipment 
is installed does not exceed 4 Pa (0.04 mbar). 
This can be achieved whenever the air needed for
combustion is able to enter through openings that
cannot be sealed, for example in doors, windows,
incoming/exhaust air wall boxes or other technical
means.

6. Assembly instructions

AH 600-990

FD xxxx

xxxx

AC 220 V

60 Hz

345 W

xxxx

160 W

35 W

3 x 50 W

Summary of Contents for AH600990

Page 1: ...Operating and Assembly Instructions AH 600 990 Coanda Extractor Hood 0 0 1 2 3...

Page 2: ...ing principle Page 5 6 2 1 Structure of the appliance Page 5 2 2 Accessories special accessories Page 5 2 3 Operating principle Page 6 3 Operation Page 7 8 3 1 Switching on and off Page 7 3 2 Special...

Page 3: ...the appliance On the following page you will find important notes on safety and operation These will serve to ensure your personal safety and the lasting value of your appliance You will find notes on...

Page 4: ...th water pressure because this poses a risk of short circuits Isolate the appliance from the mains during every maintenance operation To do this remove the mains plug or actuate the correspon ding fus...

Page 5: ...ng the appliance for the first time Remove the packaging from the appliance and dispose of it properly Pay attention to the fact that there are accessories in the packaging Keep packaging elements out...

Page 6: ...key 6 Ventilation level display 7 Coanda level key 8 Light control knob 9 Ventilation level control knob 10 After running key 11 After running symbol 12 Grease filter saturation symbol 13 Coanda leve...

Page 7: ...rcoal filter special accessory must be installed The fan in the extractor hood sucks in kitchen vapours and returns them to the kitchen after purification in the grease and activated charcoal filter T...

Page 8: ...ny time To do this turn the Light control knob to the Light position Switching on the Coanda level Turn the Ventilation level control knob to the level you require Press the Coanda level key The level...

Page 9: ...the intensive level for a few minutes and then switches off automatically Ending the intensive level prematurely Turn the Ventilation level knob to the 0 position or turn the Ventilation level knob to...

Page 10: ...maximum temperature of 65 C Place the grease filters vertically in the dishwasher to ensure that no food remainders will stay on them Slight discoloration can occur when cleaning the grease filters in...

Page 11: ...he two tabs in the downward direction and remove the activated charcoal filter from the hood in the downward direction see Fig 14 Replace the old activated charcoal filter by the new one Install in th...

Page 12: ...ender all warranty claims null and void Lamp replacement Caution Disconnect the power supply before replacing lamps Caution Lamps may still be hot shortly after use Risk of burns Remove the grease fil...

Page 13: ...rved when installing the hood The minimum distance from the worktop to the bottom edge of the wall hood is for electrical appliances 600 mm and for gas appliances 670 mm The wall hood was conceived fo...

Page 14: ...n Air recirculation You need the following accessories to install the air recirculation hood KF 600 090 activated charcoal filter Depending on the ceiling height the following duct units are at your d...

Page 15: ...holes for the hood fix the two hooks e with the countersunk screws d Make sure that the hooks lie flatly on the wall In certain circumstances you may have to countersink the drill holes Fit the includ...

Page 16: ...op of the chimney into the base Make sure that the fastening holes on the side are at the top Secure the top duct unit with 2 screws on the ceiling holder Pull the shoe down into its final position Fi...

Page 17: ...the hood fix the two hooks e with the countersunk screws d Make sure that the hooks lie flatly on the wall In certain circumstances you may have to countersink the drill holes Fit the included dowels...

Page 18: ...the 6 screws 3 5 x 9 5 mm Fig 26 Fit the top of the chimney into the base Make sure that the fastening holes on the side are at the top Secure the top duct unit with 2 screws on the ceiling holder Pul...