GAC LSM200 Series Manual Download Page 7

7

Governors America Corp. © 2021 Copyright All Rights Reserved

LSM200 Series Load Sharing Modules  6-2021-B1   PIB4100 

5

INITIAL ADjUSTMENTS (CONTINUED)

The LSM200 Series may be used with other types of GAC load sharing modules, where an external mains auxiliary parallel cable relay 

already exists. Connect Terminals 13 and 14 together permanently, closing the internal parallel cable relay and treat the parallel cable 

as external series contacts.  

NOtE: 

The smooth ramping function during paralleling will not be available under these circumstances.

 

PARAllEliNG WitH OtHER GAC lOAD SHARiNG MODUlE

Individual generator control is a main function of the LSM200 Series.  Opening and closing a switch at Terminals 16 and 17 loads and 

unloads the generator. Two LEDs (LOAD and UNLOAD) indicate the status for the operator.  The Typical operation is:

• 

When a group of engines are operating together in a load sharing mode, and one engine needs to be removed from service, the 

ILC unload switch is closed (Terminals 16 and 17). 

• 

The selected generator will start to reduce power until it gives up all its load and is held at zero power at which time it can be re-

moved from service by opening its generator circuit breaker. 

• 

The speed at which the unit reduces its load is controlled by the ILC LOAD l UNLOAD RAMP adjustment. This control adjusts the 

unloading rate, and thus the smoothness, at which the load transition occurs. 

• 

The generator can be held at zero power indefinitely. If the ILC switch is opened, the generator will increase its load and smoothly 

ramp back up to normal power.

Once a generator is removed from service, the ILC switch must be opened so the system will smoothly parallel and accept load when 

the generator is put back into service. When re-paralleling a generator set (ILC open), the LSM201 will match the existing parallel cable 

voltage with its own so that a smooth connection is made (zero voltage difference). The load control will ramp to equal load sharing. See 

details in 

Load Sharing Mode

.

The load anticipation function improves the governor response to loads applied to parallel generators. The basic transient response of 

the system is improved because the electrical load is measured directly by the LSM. This load occurs before the speed changes and 

thus the response delays are reduced. The internal LOAD ANTICIPATION adjustment allows the operator to adjust the magnitude of 

the response to the load change that is presented to the governor. A CW adjustment increases the magnitude of the compensation. 

Transient reductions of 10 - 30 % are possible if the capability of the engine is not limiting the system. Optimize this adjustment with 

repetitive load steps.

 ilC (iNDiviDUAl lOAD CONtROl) AND lOAD RAMPiNG

 lOAD ANtiCiPAtiON FUNCtiON

Solder a jumper wire across these posts without damaging the circuit board. When a reverse power condition occurs, the internal relay will 

activate and latch. To reset the relay, open the external Reverse Power Relay switch between Terminals 18 and 19. 

The reverse power monitor also offers a time delay adjustment. The time delay is an inverse function where the higher 

the reverse power, the shorter the delay in the monitor’s operation. This provides faster response if a major reverse 

power condition occurs.  Set the time delay to the shortest delay (maximum CCW) unless a long delay is required.

10 A Form C NO and NC relay contacts are provided at Terminals 25, 26, and 27 to operate the external protection 

mechanisms that remove the generator from service once a reverse power condition has occurred.  LEDs signal the 

reverse power monitor relay’s condition.

 

REvERSE POWER MONitOR (CONtiNUED)

use caution in setting the reverse power adjustment to prevent damage to the generator from excessive delay 

The generator power control feature is intended to be used when the generator is supplying power to the infinite main bus (exporting 

power). See Section 4 Wiring diagrams. In this mode, a temporary connection is made across the parallel cable at Terminals 10 and 11. 

After synchronizing and paralleling to the mains, the parallel enable switch (Terminals 13 and 14) must be closed when the main generator 

circuit breaker is closed.

The GENERATOR POWER CONTROL Adjustment can be turned CW toward 100. This will cause the generator to start supplying power 

to the mains. The generator power output is a function of how far the ADJUST control is turned CW and how high the load sensitivity con-

trol is adjusted. Once this setting is made, the power output can be reduced to zero with a switch connection between Terminals 15 and 

16. The power setting can also be set externally with a simple potentiometer and a switch that applies a voltage to Terminal 15.

This power control function can be ramped for smooth operation. Adjustment of the RAMP control towards 100 will slow down the load 

pickup time. The load up and load down times are about the same. For fast response, temporarily connect Terminals 20 and 21.

 MAiNS POWER CONtROl

The LSM200 Series operate as isochronous systems, with no internal available droop. Droop can be required add 1 MΩ across the 

parallel cable to add <1% droop. Lower values of resistance with provide increased values of droop. 

NOtE

: If droop is used, the automatic load/unload individual load control functions will not operate. 

 

DROOP

Summary of Contents for LSM200 Series

Page 1: ...nest electric governors have minor frequency differences among units to be paralleled which would cause power variations In this case one generator set would continuously increase the power it produces while the other sets would decrease the power they produce This condition eventually leads to motorizing one or more generator engines The load sharing system continuously adjusts the governor speed...

Page 2: ...nerator sets that are to be synchronized must be tested independently for their maximum capabilities Information should be gath ered for reference if operational issues arise after installation of this product Read this entire installation manual before starting installation of this product An overspeed shutdown device independent of the governor system should be used to prevent loss of engine con...

Page 3: ...erator Electrical connections are illustrated in the wiring diagrams Choice of a proper wire size is dependent on the maximum current expected at specific terminals of the load sharing module Large gauge wire should be used for Current Transformer CT Terminals 4 to 9 as the current can reach a maximum of 5 A Long wires with high resistance can add to the burden of the CT shielded wire is recommend...

Page 4: ...4 Governors America Corp 2021 Copyright All Rights Reserved LSM200 Series Load Sharing Modules 6 2021 B1 PIB4100 LSM201N STANDARD FILTERING 4 WIRING ...

Page 5: ...s common mode signals Battery minus for all generators must be connected together to limit high common mode signals indicating an unbalanced load condition Each load sharing unit takes action to control its governor to minimize this imbalance The imbalance should be less than 2 when the system is adjusted properly The parallel cable voltage is proportional to the load on the generator The voltage ...

Page 6: ...osition 100 the delay is about 30 s An internal relay with 10 A Form C contacts normally open NO and normally closed NC are included at Ter minals 28 29 and 30 along with an LED to signal the monitor relay status 1 Always set the ON point first with the delay set to minimum delay With the ON adjustment at a setting of 80 adjust the generator load for a desired trip point i e 90 load Turn the ON ad...

Page 7: ... are possible if the capability of the engine is not limiting the system Optimize this adjustment with repetitive load steps ILC Individual Load Control and Load Ramping Load Anticipation Function Solder a jumper wire across these posts without damaging the circuit board When a reverse power condition occurs the internal relay will activate and latch To reset the relay open the external Reverse Po...

Page 8: ...ay Full CCW Fastest Load Sensitivity 100 Most Sensitive Load Anticipation 0 0 External Power Meter Cal 100 Max Range ILC Load Ramp 20 Approx 4 Sec Generator Power Ramp 0 0 Generator Power Adjust 0 0 Generator Power Display Cal 50 5 Amps Full Scale Terminal Voltage Measurement Value 31 to 23 Internal Power Supply 10 6 0 2 V DC 12 to 23 Output to Governor 5 0 0 1 V DC Terminal Voltage Measurement Va...

Page 9: ...ent from 100 slowly toward 0 until the monitor turns on Remove the generator load The monitor should turn OFF reset Recheck the setting by applying the 10 load again The Reverse Power Delay may now be set by turning this adjustment CW The minimum delay necessary should be used otherwise leave this setting to full CCW minimum delay Note The delays are of the inverse time type See previous descripti...

Page 10: ... above readings look for an open generator neutral connection missing AC current or AC voltage signal or SW1 voltage range switch set improperly 10 To confirm that the Load Sharing portion is controlling the governor temporarily connect a jumper across Terminals 10 to 11 and short Terminals 13 to 14 11 Apply load to the engine The speed of the engine should fall droop as more load is applied to th...

Page 11: ...ded to use shielded cable for all external connections Be sure that only one end of the shields including the speed sensor shield is connected to a single point on the case of the speed control unit Mount the speed control to a grounded metal back plate or place it in a sealed metal box Radiation is when the interfering signal is radiated directly through space to the governing system To isolate t...

Reviews: