EEG6500 Enhanced Electronic Governor
05.09.18
PIB 5010
F
LIGHT FORCE GOVERNOR
Turning the “Light Force Governor”, (
LFG)
feature ‘ON’ (default is ‘OFF’) scales
the governor’s proportional response (GAIN) for the best resolution when
controlling small actuators, like the T1 ATB, ALR/ALN, 100/103/104 series and
normally closed Cummins EFC actuators. Turn the LFG feature “ON” for use
with these low current actuators. The letters “LFG” will be displayed in place of
the Primary Parameter Units when adjusting GAIN and STABILITY to indicate
the feature is ON. The LFG Feature can only be be turned ON or OFF when
the engine is not running.
LEAD CIRCUIT
Turning the “Lead Circuit” (
LEAD)
ON (default is ON) enables the governor to
be more responsive and typically increases the range of GAIN adjustement.
Turn Lead Circuit ‘ON’ when there is slow or moderate hunting at higher GAIN
settings.
OEM SAVE SETTINGS
OEM
OEM SAVE copies the currently active settings into separate OEM configuration area that can be restored at later date.
OEM RESTORE copies the settings stored from the OEM configuration area into the current settings and saves them for next power up. After restoration, unit
must be repowered to start engine.
OEM RESTORE
FACTORY RESTORE
OEM RESTORE
FACTORY RESTORE
Factory Restore loads the default settings as shipped from GAC into the current settings and saves them for next power up. After restoration, unit must be re-
powered to start engine. Factory Restore can only be done during power up.