background image

 

Manual Number 925SS-IOM-111120 Rev A

 

 

INSTALLATION, OPERATION AND 

MAINTENANCE MANUAL 

 

FIGURE 925SS 

 

DUROVENT

™ AIR RELEASE VALVES  

FOR SEWAGE & WASTEWATER 

 

TABLE OF CONTENTS 

 

Introduction 

….…………………………  2 

 

Description of Operation 

.....…………  2 

 

Receiving & Storage 

.....………………  2 

 

Installation  .....

.………………………….  2 

 

Valve Construction 

......……………….  3 

 

Preventive Maintenance 

....…………..  3 

 

Testing/Trouble Shooting 

...……………  3 

 

Disassembly 

....…………………………  3 

 

Assembly 

....…………………………….  4 

 

Backflushing Instructions 

……………  4 

 

Order Replacement Parts 

……………..   5 

 

Repair Kits 

………………………………   5 

 

Warranty 

.………………………………..  5 

 

Figure 925SS Drawing/Parts List 

….….  5 

 

 

 

 

234 Clay Avenue 

• Mars, PA 16046 USA 

Telephone (724) 776-1020 

• Fax (724) 776-1254 

E-mail: 

[email protected]

 

 

Summary of Contents for DUROVENT FIGURE 925SS

Page 1: ... 2 Description of Operation 2 Receiving Storage 2 Installation 2 Valve Construction 3 Preventive Maintenance 3 Testing Trouble Shooting 3 Disassembly 3 Assembly 4 Backflushing Instructions 4 Order Replacement Parts 5 Repair Kits 5 Warranty 5 Figure 925SS Drawing Parts List 5 234 Clay Avenue Mars PA 16046 USA Telephone 724 776 1020 Fax 724 776 1254 E mail info ga vag group com ...

Page 2: ...d in the valve RECEIVING AND STORAGE Inspect the valve upon receipt for damage during shipment Carefully unload all valves to the ground without dropping The valves should remain in a clean dry and weather protected area until installed For long term storage greater than 6 months the rubber surfaces of the seat should be coated with a non toxic lubricant such as SuperLube made by Synco Chemical Do...

Page 3: ... Valve operation can be easily tested Close the inlet isolation valve and remove or loosen the pipe plug nearest the inlet to drain the water from the valve The float should drop as the water leaves the valve NOTE A manual valve can be installed in place of the pipe plug to facilitate testing valves are included with backflushing attachments Replace or tighten the pipe plug and slowly open the inl...

Page 4: ... to one end of float rod threads and Install lock washer 9 and float rod 21 into float ball 20 and tighten Apply Loctite 263 to the threads on the other end of float rod Install pivot link 15 lock washer 9 and hex nut 8 on opposite end of float rod 19 and tighten Attach pivot link 15 to float arm 12 using spring pin 13 Verify free movement of linkage mechanism and that the orifice button 7 presses...

Page 5: ...nt Air Release Valve Parts List Item Description Standard Material 1 Body 316 Stainless Steel 2 Cover 316 Stainless Steel 3 Leverage Bracket 316 Stainless Steel 4 Orifice 316 Stainless Steel 5 Bracket Screw 304 Stainless Steel 6 Lock Washer 410 Stainless Steel 7 Orifice Button Buna N Rubber SS 8 Hex Nut 304 Stainless Steel 9 Lock Washer 410 Stainless Steel 10 O Ring Buna N Rubber 11 Lever Arm 316 ...