11.2 Serial Communications Option
The MCT serial interface uses Modbus RTU protocol. Any device used to communicate with the MCT over the
serial interface must use this protocol.
The MCT communication address and parity can be set on the communications screen. All other
communication settings are fixed. The port settings of the device used to communicate with the MCT must be
set to match in order for the communications to take place.
Address:
1-247 (user selectable)
Baud Rate: 9600
Data Bits:
8
Stop Bits:
1
Parity:
None, Odd, Even (user selectable)
The Modbus address is used to identify the MCT on the serial link. When a multi-drop connection is used, each
controller on the link must have a different address so that each one can be identified separately. If two or more
MCT controllers have duplicate addresses, communications with those controllers will fail because they will
each try to respond to the same message. For single MCT connections, the address only needs to match that
of the commands being sent from the host device.
Summary of Contents for MCT-CM
Page 20: ...MCT CM 20...
Page 24: ...MCT CM 24...
Page 45: ...MCT CM 45...
Page 187: ...MCT CM 187...
Page 227: ...MCT CM 227 A 4 Control Module Specifications Main CPU...
Page 228: ...MCT CM 228...
Page 229: ...MCT CM 229...
Page 230: ...MCT CM 230...
Page 231: ...MCT CM 231 Analog I O Card...
Page 232: ...MCT CM 232...
Page 233: ...MCT CM 233 Digital Input Card...
Page 234: ...MCT CM 234...
Page 235: ...MCT CM 235 Digital Output Card...
Page 236: ...MCT CM 236...
Page 237: ...MCT CM 237 Dual Communications Card Barcode and Remote Display Communication Cartridges...
Page 238: ...MCT CM 238 A 5 Power Supply Specifications...
Page 239: ...MCT CM 239...
Page 240: ...MCT CM 240 A 6 Power On Delay Relay Specifications GE1A C10HA110...
Page 241: ...MCT CM 241...