Precautions for Safe Use
●
To use the battery safely and properly, be sure to read the instruction manual before use.
*
Actual colors may differ slightly from those in the photo due to printing limitations.
The illustrations in this catalog are conceptual images.
ISO9001 certified
JQA-1118
(THE FURUKAWA BATTERY
CO., LTD.)
(Iwaki and Imaichi Plants)
ISO14001 certified
JQA-EM0380
■
For stationary batteries, ensure that the room is well ventilated so that the hydrogen concentration is 0.8% or less.
Failure to do so may cause fire or explosion.
■
Do not install the battery in a poorly-ventilated area where the hydrogen concentration becomes more than 0.8% or near open flame.
Doing so may cause fire or explosion.
Danger
Caution
FCP-SERIES
Long-life Valve Regulated Lead-acid battery for cycle use
■
The service temperature range of the battery is from -15 to 45ºC. Using the battery outside this range may accelerate deterioration
or cause the battery to freeze or overheat, resulting in damage or deformation.
■
Do not use this battery where it is exposed to direct sunlight. Doing so may cause the parts of the battery to deteriorate.
■
Do not expose the battery to water or seawater. Doing so may cause damage to the battery or fire, or cause the terminals or
connecting plates to corrode.
■
Do not use the battery near a heat source. Doing so may cause damage to the battery or cause the battery life to shorten.
■
Do not use the battery in dusty areas. Doing so may cause a short-circuit.
■
Charge the battery under the charging conditions recommended by Furukawa Battery. Failure to do so may result in insufficient
charging, electrolyte leakage, temperature rise, explosion, deterioration in performance, or reduced service life.
■
Ensure that the maximum discharge current is not exceeded for more than 1 minute for 3C
10
A or for more than 5 seconds for
6C
10
A. Failure to do so may cause damage to the battery.
■
Periodically inspect the battery. If the results deviate from the standards specified in the instruction manual, follow the steps in the
instruction manual. Using the battery with such deviations may cause damage to the battery, or burnout.
http://www.furukawadenchi.co.jp/