FULTON RM7895A Manual Download Page 21

RM7895A RELAY MODULE

21

32-00122-01

a. Simulate a flame to cause the flame signal volt-

age level to be at least 1.25 Vdc for 40 seconds 
after entry to STANDBY and also simulate a 
flame signal for 30 seconds during PREPURGE.

b. Safety shutdown will occur.

3.

Failure to ignite pilot.
a. Close pilot and main fuel manual shutoff 

valve(s).

b. Depress the reset push button.
c. Start the system.
d. Automatic pilot valve(s) should be energized but 

the pilot cannot ignite.

e. Safety shutdown will occur.

4.

Failure to ignite main.
a. Open the manual pilot valve(s); leave the main 

fuel manual shutoff valve(s) closed. 

b. Depress the reset push button.
c. Start the system.
d. Pilot should ignite and the flame signal should 

be at least 1.25 Vdc but the main burner cannot 
light.

e. Close the manual pilot valve(s).
f.

Flame signal should drop below 1.25 Vdc within 
three seconds after pilot goes out.

g. Safety shutdown will occur.

5.

Loss of flame during RUN.
a. Open the main fuel manual shutoff valve(s). The 

manual pilot shutoff valve(s) must also be 
opened. 

b. Depress the reset push button.
c. Start the system. Startup should be normal and 

the main burner should light normally.

d. After the sequence is in the normal RUN period 

for at least ten seconds with the main burner fir-
ing, close the manual main and pilot fuel shutoff 
valves to extinguish the main burner flame.

e. The flame signal should drop below 1.25 Vdc 

within three seconds after the main flame goes 
out.

f.

Safety shutdown will occur.

IMPORTANT

1. If the RM7895 fails to shut down on any of these 

tests, take corrective action (refer to 
Troubleshooting, RM7895 diagnostics and return 
to the beginning of all Checkout tests).

2. When all Checkout tests have been completed, 

reset all switches to original states.

TROUBLESHOOTING

RM7895 Diagnostics

Troubleshooting control system equipment failures is 
easier with the RM7895 self-diagnostics and first-out 
annunciation. In addition to an isolated spst alarm relay 
(audible annunciation), the RM7895 provides visual 
annunciation by displaying the ALARM LED.

Self-diagnostics of the RM7895 enables it to detect and 
annunciate both external and internal system problems. 
External faults such as interlock failures, flame failures 
and false flame signals are annunciated by the RM7895, 
which energizes the ALARM LED or by using the optional 

Keyboard Display Module. The 7800 SERIES provides a 
System Annunciation Diagnostics and Troubleshooting 
manual, form 65-0233. 

The RM7895 provides diagnostic information to aid the 
service mechanic to obtain information when 
troubleshooting the system, see Table 8.

The optional Keyboard Display Module displays sequence 
status messages indicating: STANDBY, PREPURGE, PILOT 
IGN, MAIN IGN and RUN. The selectable messages also 
provide visual indication, current status, and historical 
status of the equipment such as: Flame Signal, Total 
Cycles, Total Hours, Fault History, Diagnostic Information 
and Expanded Annunciator  Terminal Status (if used). With 
this information most problems can be diagnosed without 
extensive trial and error testing. Information available in 
the Diagnostic Information file includes: Device Type, 
Device Suffix, Software Revision, Manufacturing Code, 
Flame Amplifier Type, Flame Failure Response Time, 
Selectable Jumper Configuration Status and Terminal 
Status.

Diagnostic Information Index

 The RM7895 with the optional Keyboard Display Module 
can monitor input/output terminals and can display the 
status of the terminal on the KDM.  Example: Pilot Valve 1, 
see S7800A1019 Keyboard Display Module 
Specifications. A complete terminal description and 
number are provided. The display will show the actual 
status of the terminal. If voltage is detected at the 
terminal, 1 is displayed; but if no voltage is detected at the 
terminal, 0 is displayed.

Historical Information Index

The RM7895 has nonvolatile memory that allows the 
Relay Module to retain Historical Information for the six 
most recent lockouts. each of the six lockout files retains 
the cycle when the fault occurred, the hour of operation 
when the fault occurred, and the fault message and 
burner status when the fault occurred. The Historical 
Information can be viewed by the optional S7800 
Keyboard Display Module.

SERVICE NOTE: A Lockout condition or restart of an 
RM7895 can be accomplished by pressing the reset 
push button on the RM7895, or by pressing a remote 
reset push button wired through an optional Keyboard 
Display Module, Data ControlBus™ Module, Extension 
Cable Assembly or Remote Reset Module. A power-up 
reset will cause an electrical reset of the RM7895 but 
will not reset a lockout condition.

SERVICE NOTE: Remove the access slot covers on the 
side of the Q7800A to check voltages.

WARNING

Electrical Shock Hazard.
Can cause serious injury or death.

Line voltage is present on some of the wiring 
subbase terminals. Reinstall the access slot covers 
after performing voltage checks to prevent 
electrical shock.

NOTE:

In Table 8, normal sequences are in bold type, 
while abnormal sequences are in regular type.

Summary of Contents for RM7895A

Page 1: ...c input check Dynamic safety relay test Dynamic self check logic Internal hardware status monitoring Tamper resistant timing and logic Access for external electrical voltage checks Application Flexibi...

Page 2: ...ing the current to blow the 15A fuse or breaker in event of an internal short circuit The RM7895 needs a low impedance ground connection to the equipment frame which in turn needs a low impedance conn...

Page 3: ...in Flame Signal Amplifier see Table 2 Plug in Purge Timer Cards selectable ST7800A two sec onds to 30 minutes Q7800A Wiring Subbase Accessories 203541 5 wire connector required when Keyboard Dis play...

Page 4: ...5 127 M3529 5 1 4 133 REMOVE ONLY FOR TERMINAL TEST ACCESS 1 1 BURNER CONTROL R MOUNTING FLANGE 1 2 14 NPSM LEADWIRES FACEPLATE 3 4 14 NPT M1962B 3 3 4 95 7 7 32 183 5 1 8 130 3 7 16 87 5 1 4 133 C701...

Page 5: ...terminal is not energized c No flame present at end of PFEP d Main valve terminal is energized e Internal system fault occurred f Purge card is removed g Purge card is bad 5 RUN PERIOD a No flame pres...

Page 6: ...and self checking detector are energized for the first 40 seconds during STANDBY and the last two seconds before exiting STANDBY If a flame exists a safety shutdown occurs A standard amplifier is ener...

Page 7: ...trol and the main fuel valve s 2 Two flame detectors can be connected in parallel 3 This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance wit...

Page 8: ...All wiring must comply with applicable electrical codes ordinances and regulations Wiring where required must comply with NEC Class 1 Line Volt age wiring 4 Recommended wire size and type see Table 4...

Page 9: ...quired for the RM7895 Add the required disconnect means and overload protection 2 Check all wiring circuits and complete the Static Checkout see Table 7 before installing the RM7895 on the subbase 3 I...

Page 10: ...lifier flame amplifier signal probes electrical signal voltage probes and electrical connections M3536B G L2 3 4 5 6 7 8 9 10 F L1 13 14 15 16 17 18 19 20 21 22 12 AIR FLOW INTERLOCK MASTER SWITCH IGN...

Page 11: ...Fig 8 2 Insert the two interlocking ears into the two mating slots and with a hinge action push on the upper corners of the Dust Cover to secure it to the RM7895 3 Be sure the Dust Cover is firmly in...

Page 12: ...ut Causes for hold conditions in the INITIATE sequence are AC line dropout is detected AC line frequency error caused by using a 60 Hz device on a 50 Hz line or vice versa devices with a date code pri...

Page 13: ...If 10 second PFEP is chosen main valve terminal 9 is turned on as soon as flame is sensed Ignition terminal 10 is de energized as soon as the main valve is energized The pilot valve remains energized...

Page 14: ...red correctly and that the external controllers limits interlocks actuators valves transformers motors and other devices are operating properly IMPORTANT Do not perform a dielectric test with the RM78...

Page 15: ...oltage at terminal 6 1 Limits 2 Burner controller 3 4 5 7 L2 1 Burner motor fan or blower starts 2 Line voltage at terminal 7 within 10 seconds 1 Burner motor circuit a Manual switch of burner motor b...

Page 16: ...the flame detector s in the FINAL position Equipment Recommended Volt ohmmeter 1 Mohm volt minimum sensitivity with 0 300 Vac capability 0 6000 ohm capability 0 10 Vdc capability Checkout Summary Pre...

Page 17: ...e rod make sure Ground area is large enough Flame rod is properly located in the flame Temperature at the flame rod insulator is no greater than 500 F 260 C 4 For all optical detectors clean the detec...

Page 18: ...16 10 If the main burner flame is not established within five seconds or the normal lightoff time specified by the equipment manufacturer close the manual main fuel shutoff valve s 11 Recycle the sys...

Page 19: ...ents for flame stability and input rating e Shut down the system by lowering the set point of the operating controller Make sure the burner flame goes out and all automatic fuel valves close Proceed t...

Page 20: ...cessary to construct a barrier to block the ignition spark from the detector view Continue adjustments until the flame signal due to ignition spark is less than 0 5 Vdc NOTE The Honeywell Q624A Solid...

Page 21: ...Troubleshooting manual form 65 0233 The RM7895 provides diagnostic information to aid the service mechanic to obtain information when troubleshooting the system see Table 8 The optional Keyboard Disp...

Page 22: ...STANDBY until the line voltage is at a sufficient level for proper operating parameters STANDBY The LED indicates the burner status POWER The burner can be placed in STANDBY by opening the burner swi...

Page 23: ...es shall be connected to the Burner Controller DDL line License agreement Copying and reverse engineering is prohibited by the law PURGE HOLD Airflow Interlock The LED indicates the burner status POWE...

Page 24: ...RM7895A RELAY MODULE U S Registered Trademark 2018 Honeywell International Inc 32 00122 01 M S Rev 08 18 Printed in United States...

Reviews: