ANATEL
"This product is homologated by ANATEL, in accordance with the procedures regulated by Resolution
242/2000, and meets the technical requirements applied."
«This equipment operates on a secondary basis, that is, it is not entitled to protection against harmful
interference, even from the same type of stations, and may not cause interference to systems operating
on a primary basis."
SERIAL / WI-FI CONVERTER
TCP485WIFIV01-01T
-16374
TCP-485 WiFi
V
er
.01
1. DESCRIPTION
The Serial/Wifi converter
TCP-485 WiFi
allows the interconnection of the Full Gauge controllers
with the supervisory software Sitrad through a WiFi data network using the TCP/IP communication
protocol currently.
Many companies have Wireless routers in their facilities, and it is posible to use this same network for
data traffic between controllers and Sitrad supervisory software, using the
TCP-485 WiFi
converter.
3. TECHNICAL ESPECIFICATIONS
Operating temperature
0 to 50ºC / 32 to 122ºF
Operating humidity
10 to 90% UR (without condensation)
32 (without the need for termination)
4. INDICATIONS
5. INDICATIONS AND KEYS
Have this manual in your hands
using the
FG Finder
application.
Converter power
External power supply 12 Vdc / 1A
Number of instruments supported
per converter in the RS-485 network
Antenna
3,8dBi for a estable high quality connection
Product dimensions
43,5 x 16 x 34 mm (LxAxP)
Compatibility
IEEE 802.11 b/g up to 54 Mbps
Encryption type
WEP, WPA and WAP2
2. APLICATIONS
• Facilities where it is desirable to use the existing Wireless network;
• Facilities that do not have conditions for passing a new Ethernet data cabling;
• Facilities where the cost of the investment in the cabled structure has an impact;
Note:
The
TCP-485 WiFi
converter is designed to work only with Full Gauge Controls
instruments.
Antenna - Connect the antenna
supplied with the converter.
NOTE:
Use only antenna supplied by
Full Gauge.
Converter power
Reset - see item 7 - Reset configuration
Communication network with RS-485 instruments
Power indication
LED - Power and
signal strength
indication LED
Status indication
LED - connection
status indication
LED
RS-485 network
t r a n s m i s s i o n
indication LED
RS-485 network
r e c e p t i o n
indication LED
Antenna dimensions
34,9 x 175,2 x 13 mm (LxAxD)
Supervisory
system
Wi-Fi
Serial
comunication
RS
485
Ocurrence
White / On
Contact Full Gauge Controls
Router connection password error
Equipament scanning the network
LED STATUS / State
LED POWER / State
TCP-485 WiFi
ALL MODES
CONFIGURATION
MODE
Contact Full Gauge Controls
Equipament ready to connect
Excellent signal level
No signal
Connected with Sitrad and communicating
Good signal level
Poor signal level
Very poor signal level
Equipament booting
White / On
Equipament connected and ready to be configured via internet browser
White / Flashing
Off
Red / On
Green / Flashing
Yellow / Flashing
Off
Red / Flashing
Red / Flashing
Red / On
Yellow / On
Red / On
Yellow / Flashing
Green / On
Blue / Flashing
Purple / Flashing
Blue / Flashing
Yellow / On
Blue / Flashing
Purple / On
Blue / Flashing
Red / On
Blue / On
Red / Flashing
Blue / Flashing
OPERATION
MODE
Power supply provided with the
converter
Input - 100-240Vac (50/60Hz)
Output: 12Vdc / 2A
WARNING
ACCESSORIES:
Only use original accessories of Full Gauge Controls.
If you have any questions, please contact our technical support.
AUTHORIZED SERVICES:
The installation and maintenance of the product must only be performed by qualified personnel.
DUE TO CONSTANT EVOLUTION, FULL GAUGE CONTROLS RESERVES THE RIGHT TO CHANGE THE
INFORMATION CONTAINED IN THIS MANUAL.
BEFORE INSTALLING THE CONTROLLER WE RECOMMEND READING THE INSTRUCTION
MANUAL THOROUGHLY IN ORDER TO AVOID POSSIBLE DAMAGES TO THE PRODUCT.
PRECAUTIONS WHEN INSTALLING THE PRODUCT:
Before performing any procedure in this instrument, disconnect it from the mains; make sure the
instrument has proper ventilation, avoiding installation in panels containing devices that may force
it to work outside the specified temperature limits;
Install the product away from sources that can generate electromagnetic disturbances, such as:
motors, contactors, relays, solenoid valves, etc.