DIGITAL CONTROLLER FOR

REFRIGERATION AND DEFROST

TC-900Ri 

power

 

4. CONFIGURATIONS

- Press             for 2 seconds until appears               , and release it after that. The adjusted operation 
temperature will appear. 
- Use         and         to change the value and then press           to record it.

4.1 - Control temperature adjust (SETPOINT):

SET

SET

1. DESCRIPTION

TC-900Ri 

power

 is a control for low temperature ventilated units which automates defrosting 

processes, providing great energy saving

2. APPLICATION

• Counters
• Refrigerating balconies

3. TECHNICAL SPECIFICATIONS

- Power supply: 

TC-900Ri

 

power: 115 or 230Vac ±10%( 50/60 Hz)  

                           TC-900RiL power: 12 or 24 Vac/dc

- Control temperature:

 -50 to 75° C / -58 to 167°F

- Operating temperature: 

0 to 40°C / 32 to 104°F

- Operating humidity: 

10 to 90% RH (without condensation)

- Resolution: 

0.1°C  from -10 to 75°C and 1°C outside this range

 

/1°F  in all range

- Load current (outputs):

 COMP: 12(8)A/240Vac 1HP (compressor, solenoid valve or contactor)                                                                    

                                          DEFR:  10A / 240Vac 1/4HP (defrost  resistance or hot gas) 
                                          FANS:  5(3)A / 240Vac 1/8HP (evaporator fans) 

- Dimensions:

 71 x 28 x 71mm

- Sensors:

S1: ambient sensor (black cable)
S2: evaporator sensor (gray cable)

. For cooling and defrosting, works with two sensors, one 

being for ambient temperatura and the other fixed to the evaporador that controls defrost ending. With 
the powerful 16-amp relay, directly controls compressors up to 1 HP. The defrost output has a 10A 
current capacity, as well as also having Normally Closed (NC) contact avaiable. It also has indicators in 
ºC  and  °F  and  digital  filters,  which  have  the  purpose  of  simulating  an  increase  in  mass  in  the 
environment  sensor  (S1),  thus  increasing  its  response  time  (thermal  inertia)  and  preventing 
unnecessary activations of the compressor.
Product complies with UL Inc. (United States and Canada) and NSF (United States).

4.2 - Parameters table

Description

Fun

Access code:123 (one hundred and twenty-three)

Control differential (hysteresis)

Offset indication for ambient sensor

Minimum setpoint allowed to the end user

Maximum setpoint allowed to the end user

Delay when the instrument is powered on

Act point of high ambient temperature alert

Refrigeration time (interval between defrosts)

Compressor delay after on (on - off)

Compressor delay after off (off - on)

Compressor status with detached ambient sensor (S1) 

Defrost when the instrument is powered on 

Evaporator temperature (S2) for end defrost

Maximum duration of defrost (for security)

Fan turned on during defrost

Defrost type

Min

Max

Unit

Standard

CELSIUS

FAHRENHEIT

-

0.1

-20.0

-50.0

-50.0

0

-50.0

1

0

0

0 - off

0 - no

-50.0

0=disable

0 - no

0 - electric

-

 1

 -36

 -58

 -58

0

 -58

1

0

0

0 - off

0 - no

 -58

0=disable

0 - no

0 - electric

-

20.0 

20.0

75.0 

75.0 

30

75.0 

999

999

999

1 - on

1 - yes

75.0

90

1 - yes

1 - hot gas

-

 36

 36

 167

 167

30

167

999

999

999

1 - on

1 - yes

167

90

1 - yes

1 - hot gas

-

º C 

º C

º C 

º C

min.

º C 

min.

sec.

sec.

-

-

º C 

min.

-

-

-

1.5

0

-50.0

75.0

0

40.0

240

0

0

1 - on

0 -no

40.0

45

0

0

-

 °F

°F

 °F

 °F

min.

 °F

min.

sec.

sec.

-

-

 °F

min.

-

-

-

3

0

-58

167

0

104

240

0

0

1 - on

0 -no

104

45

0

0

Min

Max

Unit

Standard

4.3 - Parameters description

F01 - Access code (123)

To change the parameters it is necessary to use the access code.It is not necessary to use the access 
code  to visualize the adjusted parameters. 

F02 - Control differential (hysteresis)

It is the difference of temperature (hysteresis) between to turn OFF and turn ON the refrigeration output.
Example: To control the temperature in 4.0°C with differential of 1.0°C. Soon, the refrigeration will be 
turned off in 4.0°C and turned on again in 5.0°C (4.0 + 1.0)

F03 - Offset indication for ambient sensor

It allows to compensate eventual shunting lines in the reading of ambient temperature (S1) proceeding 
from the exchange of the sensor or  cable length alteration.

F04 - Minimum setpoint allowed to the end user
F05 - Maximum setpoint allowed to the end user

Electronic  limits  whose  purpose  is  to  prevent  that  too  high  or  too  low  setpoint  temperatures  are 
regulated.

F10 - Compressor delay after off (off-on)

It is the minimum time that compressor will keep off, it means, space of time between the last stop and 
the next drive. It serves to alliviate the discharge pressure and to increase the time of useful life of the 
compressor.

F11 - Compressor status with detached ambient sensor (S1)

If the ambient sensor (S1) will be damaged or outside the specified range, the compressor assumes the 
configured status in this function.
Example: For counters of fruits, it is better to keep the compressor off. In counters of meat it is better to 
keep the compressor  on.

F12 - Defrost when the instrument is powered on

It  makes  possible  the  accomplishment  of  a  defrost  at  the  moment  that  controller  is  energized,  for 
example, in the return of electrical energy (in case of energy lack)

F13 - Evaporator temperature (S2) for end defrost

If the temperature in the evaporator (sensor S2) reaches the adjusted value, the end of defrost will be for 
temperature. With this, the defrost process is optimized.

F06 - Delay when the instrument is powered on

When the instrument is powered on, its control is kept disabled during a time, delaying the start of 
process. During this time, it works only as temperature indicator. It serves to prevent demand of electric 
energy peaks, in case of lack or return of the same and when exists a lot of equipment connected on the 
same net. For this, just adjust different times for each equipment. This delay may be of compressor or 
defrost (when exist defrost on turn on).

F07 - Act point of high ambient temperature alert

If the ambient temperature (sensor S1) reaches this point during refrigeration, this will be signaled 
visually through the indication blinking on display.

F08 - Refrigeration time (interval between defrosts)

It is the time which compressor will turn on and turn off only for ambient temperature and starts to be 
counted  when the  fan is turned on , after  fan-delay stage (fan return after draining).

F09 - Compressor delay after on (on-off)

It is the minimum time that compressor will keep on, it means, space of time between the last drive and 
the next stop. It serves to prevent high voltage events in the electric network.

E251415

TC-900Ri 

power

Ver.03

Locked temperature indication (S1) during defrost 

Draining time (dripping of defrost water)

Evaporator temperature (S2) for fan return after draining

Maximum time of fan return after draining (fan-delay)

Fan on with compressor off (refrigeration)

Fan stopped for high temperature in the evaporator

Time to collect the gas before start

ing

 the defrost

Intensity of the digital filter applied to the sensor 1 (0-OFF)

Time to Key blocker 

0 - no

0

-50 

0

0 - no

-50

0

0

14 - no

1 - yes

30

75.0

30

1 - yes

75.0

 999

9

60

-

min.

º C 

min.

-

º C 

sec.

-

sec.

0 - no

0

 -58

0

0 - no

 -58

0

0

14 - no

1 - yes

30

167

30

1 - yes

167

999

9

60

-

min.

°F

min.

-

°F

sec.

-

sec.

0 - no

10

0

1

1 - yes

75.0

0

0

14 - no

0 - no

10

0

1

1 - yes

167

0

0

14 - no

TC900RIPWV03-04T

-12768

COMPONENT

Reviews: