Full Gauge Controls RT-607Ri plus Manual Download Page 1

Ver.01

RT-607Ri plus

DIGITAL THERMOSTAT 

WITH EVENT SCHEDULE

1. DESCRIPTION

Digital temperature controller and display conjugated to a time programmer with up to four daily events, 
all with adjustable start and end. Its internal quartz synchronizer clock remains accurate for more than 
60 years, even at frequent and often long power shortages.

®

Through serial output, the RS-485 allows communication with SITRAD  software, which makes its 
configuration simple and fast.
Product complies with UL Inc. (United States and Canada).

2. APPLICATION

• Defreeze at set times
• Air-conditioning
• Water heaters
• Counters with static coil

3. TECHNICAL SPECIFICATIONS

- Power supply:

RT-607Ri plus  -  115 or 230Vac ± 10% (50/60Hz)
RT-607RiL plus  - 12 or 24 Vac/dc

- Control temperature:

-50 to 105°C

-

58 to 221°F

- Resolution:

0.1°C between -10 e 100°C and 1°C in the rest of the range
1°F between -58 and 221°F

- Dimensions: 

71 x 28 x 71mm

- Operating temperature:

 0 to 60°C / 32 to 140°F

- Operating humidity: 

10 to 90% RH (without condensation)

- Sensors: 

 S1- Thermostat sensor (black)

- Control outputs:

THERM - Thermostat control output  - 10A / 240Vac 1/4HP 
EVENT - Event schedule activation output - 10A / 240Vac 1/4HP 

4. CONFIGURATIONS

4.1 - Control temperature setting (SETPOINT)

Press        for 2 seconds until           , appears, and then release the key. The set working temperature 
will appear. Use the        and        keys in order to change the value and, when ready, press        to 
record.

4.2 - To enter into the functions menu

Press           and           simultaneously for two seconds until it               , appears, then releasing it. When
          appears, press         (short hit) and enter the code (123) through keys        and        . To confirm, 
press the key             . Through keys           and           access the other functions and proceed in the same
manner to adjust them.
To leave and return to normal operations, press         (long hit) until            appears.

SET

SET

SET

SET

SET

4.3 - Functions

Access code entry
Advanced configuration functions
Events planner operating mode
Scheduling in the events planner
Adjustment of the clock and the day of the week

Description

Min

Max Unit

CELSIUS

Standard

Standard

Min

Max Unit

FAHRENHEIT

0.1

-5.0

-50.0 

-50.0

0

0-no

0

1

20.0

5.0

105.0

105.0

999

1-yes

999

247

°C

°C

°C 

°C

-

sec.

min.

-

Temperature control differential (hysteresis)

Indication Offset

Minimum limit of adjustable temperature 

Maximum limit of adjustable temperature 

Operation mode for the thermostat

Minimum time of off thermostat output 

Hitch thermostat to event schedule

Manual activation time for events output

Address of the instrument on the network RS-485

1.0

0

-50.0

105.0

0

0-no

0

°F

°F

°F 

°F

-

sec.

-

min.

-

36

9

221

221

999

1-yes

999

247

1

-9

-58

-58

0

0-no

0

1

2

0

-58 

221

0

0-no

0

1

4.4 - Parameters table

4.4.1 - Parameters description

Temperature control differential (hysteresis)

It is the temperature difference (hysteresis) between turning the refrigeration or heating ON and OFF.
Example: When you wish to control the temperature at 4.0 ºC with a 1.0 ºC differential. In the case of 
refrigeration, it shall be turned off at 4.0°C and turned on again at 5°C
In the case of heating, it shall be turned off at 4°C and turned on again at 3°C

Indication Offset

Permits to compensate for any possible deviations in the reading of the room temperature (S1), resulting 
from the sensor replacement or change in the cable length.

and

            

Minimum and Maximum limits of adjustable temperature 

Limits whose purpose is to avoid that, by mistake, the temperatures are exaggeratedly set too high or too 
low with relation to the setpoint.

Operation mode for the thermostat

This function allows setting the thermostat operation mode:

Refrigeration
Heating

Minimum time of off thermostat output 

Minimum time during which the thermostat output shall remain off before being reactivated. This field is 
also used as activation delay when the controller is turned on.

Hitch thermostat to event schedule 

This option allows linking the thermostat output operation (THERM) to the event schedule. If option 0 
(no) is selected, the thermostat output shall be controlled by the temperature alone.
In the case of option 1, the thermostat option shall be controlled by the temperature and may only be 
activated in a valid event in the event schedule.

Address of the instrument on the network RS-485

® 

Address of the instrument in the network for the communication with the SITRAD software. Remarks: 
in a single network, there cannot be more than one instrument with the same address.

4.4.2 - Events schedule operating mode

In this option, you can choose how the events schedule will operate.

Weekly programming

 - In this mode, the instrument can configure up to four events for every day 

of the week

Programming for business days

 - In this mode, the instrument keeps the events the same for 

business  days  (Monday  through  Friday),  and  allows  the  programming  of  different  events  for 
Saturday and Sunday.

         

Manual activation time for events output 

Time that output events is active when it is activated manually. Once this period of time is over, the output 
events returns to function automatically.

4.4.3 - Programming of the events schedule

In this option, you can enter the values for the time periods for each event. The entry of the data depends 
on the operating mode configured. You can configure up to four events for each day. For each event you 
configure the start time and the end time through options                      until                      where:

Start time for the first event
End time for the first event

Start time for the fourth event
End time for the fourth event

If you do not need to use the four events, you can configure it to be deactivated, and all you have to do is 
increase the off time (          for example) until the           indication appears. It is also possible to configure 
an event to overlap at midnight, and for that you should increase the off time until the option           appears 
and  adjust  an  event  for  the  next  day  to  start  at  00h  and  00min. According  to  the  operating  mode 
configured, the following scheduling possibilities may be presented.

Daily programming 

 - In this mode, the instrument keeps the events the same for all of the days of 

the week.

4.4.4 - Adjustment of the current time and day of the week

After entering the function menu, press key             repeatedly until the message                   appears Hit
key         . The settings will appear in the following order:
                                      

HOURS      MINUTES      DAY OF THE WEEK 

 

Ex.: 12h43min -  Friday

Hours
Minutes
Day Of The Week

5. FUNCTIONS WHIT FACILITATED ACCESS

5.1 - Visualize the current time

Quickly pressing the key       , you can visualize the time set in the controller, the current time will be 
shown, followed by the minutes and then the day of the week.           

Ex.: 12h43min -  Friday

Hours
Minutes
Day Of The Week

SET

SET

E251415

R

T607V01-08T

-10790

Fun

Reviews: