background image

F31 - Minimum setpoint allowed to the end user (4th stage): 
F32 - Minimum setpoint allowed to the end user (4th stage):

Electronic  backstop  aimed  to  prevent  exceedingly  low  or  high  temperatures  being  inadvertently 
adjusted in the setpoint.

NOTE:

 When stage 4 is defined as alarm (F30=2, 3, or 4), the activation points are defined in F31 and 

F32.

F33 - Stage 4 control differential (hysteresis):

It is the temperature difference (hysteresis) between switching output OUT4 ON and OFF.

F34 - Minimum delay to switch on stage 4 output again:

It is the minimum time the OUT4 output will remain off, i.e. the length of time between the last stop and 
the next start up. Programmed only if F30=0, 1, 5, or 6.

F35 - Alarm inhibition time upon power up:

This function serves to inhibit the alarm for a certain period after the start up, because the system has 
not yet reached the working temperature (only if F30=2, 3 or 4).

F36 - Time to reactivate the alarm when manually inhibited:

This function allows for three different configurations (only if F30=2, 3, or 4)

[Auto]

- The alarm will be inhibited until the temperature reaches the normal working condition and 

returns to the alarm condition again.

[,,,0]

- Alarm cannot be inhibited by the easy access keys.

[,,,1]

 to 

[,999]

 - Alarm will be inhibited during this period (in minutes), switching on again if the 

alarm condition persists.

F37 - Alarm on time (

[TOn,]

):

To adjust the time output OUT4 will remain active (only if F30=2, 3, or 4).

F38 - Alarm off time (

[TOFF]

):

To adjust the time output OUT4 will remain inactive (only if F30=2, 3, or 4). To always keep the alarm 
active configure this function with 0.

F39 - Time to inhibit the alarms (delay):

When this configuration is active, the temperature must remain in the alarm condition for the defined 
inhibit  time  before  the  alarm  is  indicated. This  allows  avoiding  warnings  originating  from  punctual 
temperature variations. This configuration is used in the alarm output and in the audible alarm (buzzer).

F40 - Digital filter operating mode:

[,,,0]

- The filter operates both when the temperature rises and when it falls.

[,,,1]

- The filter operates only on the ascending slope of the temperature. When the temperature 

falls the response is immediate.

F41 - Digital filter intensity:

The value adjusted in this function represents the time (in seconds) for the temperature to change by 
0.1° C. This function can be switched off by setting it at the minimum value 0.

F42 - Functions lock:

It allows and configures the functions lock (see item 6.3.2).

[,,,0]

- Do not allow the functions lock.

[,,,1]

- Allow a partial lock where the control functions will be locked but the adjustment of the 

setpoint is allowed.

[,,,2]

- Allow full locking

NOTE:

 The view of the minimum and maximum temperature records will always be allowed.

F43 - Time for functions lock:

It configures the time in seconds for the command to activate the functions lock:

[,,15]

to 

[,,60]

 - Time in seconds for the command to activate the lock.

F44 - Control functions shutdown:

Authorizes switching off the control functions (see item 6.3.3).

[,,,0]

-Disables the control functions shutdown.

[,,,1]

-Enables activation/deactivation of the control functions only if the functions are unlocked.

[,,,2]

-Enables activation/deactivation of the control functions even if the functions are locked.

F45 - Enable the soak function feature in output Out1.

[,,,0]

-Disable soak point.

[,,,1]

-Enable soak point in output OUT1.

NOTE:

 The operation of the control in the soak mode is described in item 6.3.10 of this manual.

F46 - Soak Setpoint 1 Temperature (SSP1):

Desired temperature during Soak Point 1.

F47 - Permanence time in the soak point1:

Configures the time in minutes the controller will remain in Soak Point 1.

F48 - Soak Setpoint 2 Temperature (SSP2):

Desired temperature during Soak Point 2.

F49 - Permanence time in the soak point2:

Configures the time in minutes the controller will remain in Soak Point 2.

F50 - Soak Setpoint 3 Temperature (SSP3):

Desired temperature during Soak Point 3.

F51 - Permanence time in the soak point3:

Configures the time in minutes the controller will remain in Soak Point 3.

F52 - Soak Setpoint 4 Temperature (SSP4):

Desired temperature during Soak Point 4.

F53 - Permanence time in the soak point4:

Configures the time in minutes the controller will remain in Soak Point 4.

F54 - Soak Setpoint 5 Temperature (SSP5):

Desired temperature during Soak Point 5.

F55 - Permanence time in the soak point5:

Configures the time in minutes the controller will remain in Soak Point 5.

F56 - Instrument address in the RS-485 network:

Equipment's network address for communicating with Sitrad software.

NOTE:

 One network must not have different equipment with the same address.

7. SIGNALS

Sensor disconnected or temperature outside specified range.

[Err,]

[Ctrl][On,,]

[Ctrl][OFF,]

[LOC,][On,,]

[LOC,][OFF,]

[eCAL]

[pppp]

Contact Full Gauge.

Reconfigure the function values.

A

B

MT-530

super

A

A

B

B

A B

A

B

A

A

B

B

A B

A

B

A

A

B

B

A B

Serial Interface RS-485

Device  used  to  establish  the 
connection  of  Full  Gauge  Controls 
instruments with Sitrad .

®

Instrument

RS-485 network

Grounded
terminal

External

loop

®

CONV. 32 

or

CONV. 256

A

A

B

B

A B

*CONNECTION BLOCK FOR SERIAL COMMUNICATION

It is used to interconnect more than one instrument to the Interface. The wires 
must be connected as follows: Terminal 

A

 of the instrument connected to terminal 

of the connection block, which in turn must be connected to terminal 

of the 

Interface. Repeat the procedure for terminals 

and   , with 

being the cable 

mesh (optional ground). Terminal    of the connection block must be connected to 
the respective terminals       of each instrument.

 

  

*Sold Separately

MT-530

super

Keep Sitrad up-to-date through the

site: http://www.sitrad.com.br

®

8. INTERCONNECTING CONTROLLERS, RS-485 SERIAL INTERFACE, AND COMPUTER

Control functions off.

Functions lock.

Unlocking of functions.

Control functions on.

9. OPTIONAL ITEMS – Sold Separately

EasyProg 

 or later

 

via Serial TTL connection

.

version 2

It is an accessory which has the main function of storing the controller parameters. At any time you can 
load new controller parameters unload them on a production line (of the same controller), for example.
It is provided with three types of connections for loading or unloading the parameters:

-

 

Serial RS-485:

 It is connected via RS-485 network to the controller (only for those controllers provided 

with RS-485).

- USB:

 It is connected to the computer via USB port, using the Sitrad Preset Editor. 

- Serial TTL:

 The controller may be connected directly to

EasyProg 

EASYPROG

IMPORTANT

I N   O R D E R   T O   B E   A B L E   T O  
COMMUNICATE  WITH  EASYPROG  THIS 
C O N T R O L L E R   M U S T   N O T  
COMMUNICATE WITH SITRAD.

Extension Frame

To install controllers with maximum dimensions of 76 x 34 x 77 mm (opening dimensions of 71 x 29 mm for 
installation in the extended frame) in several situations, because it does not require precision of the 
opening to embed the instrument. It allows customization through a sticker with the brand and company 
contact, in addition to being accompanied by two 10 A (250 V AC) switches that can trigger internal light, air 
curtain, on/off system or fan.

E-case

Recommended for the Evolution line, it prevents water from entering the back part of the instrument.
It protects the product when the installation site thereof is washed.

Reviews: